ENERGY CAPACITY
Nominal heat input
(0/2000ft)
MBH
122.8
Nominal heat input
(2000/4500ft)
MBH
116.7
Minimum heat input
MBH
49.5
Maximum useful output
(0/2000ft)
MBH
100.7
Maximum useful output
(2000/4500ft)
MBH
95.9
Minimum useful output
MBH
37.0
GAS SUPPLY PRESSURE
Gas
Normal
Min
Max
Natural
inwc
7.0
3.5
10.5
Propane
inwc
11.0
8.0
13.0
GAS PRESSURE AT BURNER
Gas
Min
Max
Ignition
Natural
inwc
0.8
5.3
2.4
Propane
inwc
1.4
9.0
5.2
FLUE DESIGN
Minimum Venturi pressure
inwc
0.64
Flue pipe diameter
Coaxial
in
2.25/4
3.25/5
Twin split pipes
in
3.25/3.25
Nominal heat ow rate
(0/2000ft)
MBH
122.8
Nominal heat ow rate
(2000/4500ft)
MBH
116.7
Min Exhaust temperature
°F
262
Max Exhaust temperature
°F
324
INJECTORS No. Size
Natural
14
130
Propane
14
89
GAS FLOW RATE
Gas
Min
Max
Natural
ft³/h
48.7
121.1
Propane
lb/h
2.23
5.55
CLEARANCE TO COMBUSTIBLES
Front
in
18
Back
in
0
Top
in
8
Sides
in
2
Bottom
in
8
Flue pipe enclosed
in
2
Flue pipe free air
in
0
Hot water pipes
in
1”
ELECTRICAL
Voltage
V
120
Frequency
Hz
60
Current
A
1.6
Power consumption
W
180
FLUE GAS FIGURES
Gas
Min
Max
CO2
2.5%
7.2%
O2
16.5%
8.1%