34 SAVIO HEAT ONLY MANUAL
15. Commissioning Cont.
Checking the ue system and combustion:
15.9
The ue system should be visually checked for soundness. Check all clamps, gaskets and
•
xings are secure and tight.
Ensure that the ue terminal is sited correctly in accordance with the ue tting instruc-
•
tions.
To check the exhaust gas:
Remove the plugs indicated (Fig. 15.11).
•
Insert the analyzer probe in the exhaust
•
gas sampling point or in the air intake
sampling point.
Reference tables are given in the Sec-
•
tions 2 on page 9 of this manual for proper
CO2 levels.
Figure 15.11
Air-Flue exhaust
sampling points
Instructing the user:
15.10
Hand over the User manual, this Installation,Operation and Service manual to the end user
•
and explain how to use the unit in Central Heating mode.
Take the User step by step through the lighting instructions.
•
Show the User how to switch off the appliance quickly and indicate the position of the elec-
•
tric service switch and the boiler on/off switch.
Explain the proper use and adjustment of all system controls; this will ensure the greatest
•
possible safety and fuel economy.
Explain the function and use of the function switch.
•
Explain how to turn off the appliance for both short and long periods and advise on the pre-
•
cautions necessary to prevent damage should the appliance be inoperative when freezing
conditions may occur.
Fill in the details required on the Boiler Guarantee Certi cate and hand to the User advis-
•
ing them to return the correct section for boiler Guarantee registration. Finally, advise the
User that, for continued safe and ef cient operation, the appliance must be serviced by a
competent person at least once a year.
Useful output
KW
12 14 16 18 20 22 24 26
BTU/h
40950 47750 54600 61400 68240 75064 81900 88700
Naturel
Pa
inwc.
240
0.96
320
1.28
410
1.64
500
2.00
600
2.40
710
2.85
830
3.33
950
3.81
m³/h
1.63
1.87
2.10
2.34
2.56
2.78
3.00
3.22
ft³/h
5.34
6.13
6.89
7.67
8.40
9.12
9.84
10.56
Propane
Pa
inwc.
410
1.64
540
2.16
680
2.73
840
3.37
1010
4.05
1190
4.77
1390
5.58
1590
6.38
Kg/h
1.20
1.37
1.55
1.71
1.88
2.04
2.20
2.36
lb/h
2.64
3.02
3.41
3.76
4.14
4.49
4.85
5.20
Table 15.1