Savant Power System Deployment Guide - Sol-Ark
Copyright 2022 Savant Systems, Inc
009-2222-01 | 121222
- 13 -
5.7. Solar Panels (DC Power)
Once batteries have been installed and tested, wire the Solar Panels to the MPPT inputs on the inverter. The following diagrams shows the wiring for
Sol-Ark inverters
Sol-Ark 15k
ELECTRIC SHOCK!
: Ground the panel mounts and frames via 12AWG wire before continuing.
Solar
Panel
Y-Connector
Y-Connector
Solar
Panel
Solar
Panel
Solar
Panel
Solar
Panel
Solar
Panel
Solar
Panel
Solar
Panel
IMPORTANT!:
–
Sol-Ark has triple MPPTs for three separate PV input pairs.
–
If using Y-Connectors, run two strings in parallel, totaling 26A (self-limiting)
–
Maximum PV input
is 19.5kW (± 5%) / system | 6.5kW / MPPT | MAX 500VOC PV | MAX ISC /MPPT 26A (limiting to 26A)
–
Damage will occur if PV VOC > 550V.
–
Parallel strings per MPPT must be the same voltage.
–
PV1 A/B must be the same voltage if using both strings.
–
Panels on the same MPPT can face different directions.