background image

ASV115 

 

 

Air volume parameters 

(Room positive pressure

supply

 

 

exhaust

)

 

Air volume, setpoint 

c

qV.s 

= 40% 

 

 4 V 

Master (supply air) 

min 

= 20% 

max 

= 100% 

nom 

= 1000 m³/h 

Master (exhaust air) 

min 

= 20% 

max 

= 100% 

nom 

= 900 m³/h 

c-factor 100 

(

 = 1.2 kg/m³) 

Air volume, actual value, master 

r

qv

 = 40%

 

 4 V 

 400 m³/h 

Air volume, actual value, master 

r

qv

 = 40%

 

 4 V 

 360 m³/h 

 

Air volume parameters 

(Room negative pressure

supply

 

 

exhaust

)

 

Air volume, setpoint 

c

qV.s 

= 40% 

 

 4 V 

Master (supply air) 

min 

= 20% 

max 

= 100% 

nom 

= 1100 m³/h 

Master (exhaust air) 

min 

= 20% 

max 

= 100% 

nom 

= 1000 m³/h 

c-factor 100 

(

 = 1.2 kg/m³) 

Air volume, actual value, master 

r

qv

 = 40%

 

 4 V 

 440 m³/h 

Air volume, actual value, master 

r

qv

 = 40%

 

 4 V 

 400 m³/h 

 

Example 2: VAV (Master-Slave) 

Variable air volume control with supply- and exhaust-air controller in 
master–slave configuration, commanded by a room temperature 
controller for rooms with high comfort and control requirements. The 
master–slave configuration allows an equal-percentage relationship 
between the supply- and exhaust-air volumes. 

 

www.sauter-controls.com  

11/13 

The command signal, e.g. from a room temperature controller, is 
connected to the master controller. The command signal shifts the 
parameterised air volume values in the range from 

min

 to 

max

.on 

the master controller. The actual value signal of the master control-
ler is specified as the command signal for the slave controller. This 
type of connection is also known as "schedule control". The result is 
that if there are changes to the upstream pressure in the air network 
due to fluctuations in duct pressure control, these disruptions can 
be detected and transmitted directly to the slave controller. This 
guarantees an equal-percentage relationship between the supply- 
and exhaust-air controllers. The command signal or the actual value 
signal r

qv

 from the master controller can be connected in parallel to 

several slave controllers. 

 

The required operating air volume between 

min

 and 

max

 is pa-

rameterised on the master controller. On the slave controller, 

min

 

is set to 10% and 

max

 is set to 100%. Alternatively, 

min

 and 

max

 

can be set so that 

min

 (slave) 

min

 (master) and 

max

 

(slave) > 

max

 (master). It should be ensured here that 

nom

 is 

parameterised with the same value for the master and slave con-
trollers to ensure synchronicity of the controllers. If the 

min

 and 

max

 values on the supply- and exhaust-air sides are parameter-

ised differently, undesirable negative or positive pressure may 
occur in the room. 

 

 

Setting for room positive pressure = 

supply 

 

exhaust

 

 

Setting for room negative pressure = 

supply 

 

exhaust

 

 

 

Note 
With this type of room pressure generation, the resultant room 
pressure depends on the size of 

. Defined room pressures can 

be achieved using room pressure controllers and the 

 function.

 

 
For priority control, the digital inputs on the supply and exhaust air 
controllers are activated in parallel via switching contacts. The 
desired parameters for 

min

max

 and 

mid

 are set using software. 

This method of operation is also suitable for constant air volume 
control, and this function is also achieved by a constant command 
signal at the setpoint input. 

Summary of Contents for ASV115

Page 1: ... SLC SAUTER Local Communication protocol Easy to parameterise using the SAUTER CASE VAV software Constant air volume control using parameterisable inputs Technical description Power supply 24 V Variable end values for the differential pressure s measuring range 50 150 Pa 100 300 Pa Efficient control algorithm Output signal 0 10 V for Air volume actual value rq Air volume control deviation eq or fo...

Page 2: ...nded 7 Recommend hardness of tubes 40 Sha e g silicone 8 Connection 02 can be configured as an analogue input or analogue output using SAUTER CASE VAV software 9 Digital inputs for external potential free contacts gold plated recommended 10 The parametering tool is always one of the subscribers so a maximum of 31 devices can be linked 11 Recommended Belden 3106A Accessories Type Description 052045...

Page 3: ...switching contact 1 DI04 Factory setting FS Full scale PR Room pressure TR Room temperature Heating Cooling DN Nominal diameter c o Change over ad Index ad for additive p Index p for priority V Index V for air volume s Index s for second priority q Index q for quantity Setting the air volume The following functions are generally available to operate the air volume controller Setting ranges Functio...

Page 4: ... permitted angle of the damper Functional diagram for damper position The function can be set using Sauter CASE VAV 1 4 or higher which allows one of the following applications for the device to be selected VAV 10 001 M VAV 20 001 M or VAV 20 001 Sxi When setting the parameters for terminal AO02 using the feedback signal for the damper position it is recommended to perform an adaption using Manual...

Page 5: ...ression and upward limitation is defined by the maximum possible plant air volume damper fully open As an example the calculation and setting of the parallel setpoint shift may be performed as follows In order to obtain the value for the resultant setpoint shift as a per centage of the air volume the configuration of connection AI02 must also be taken into account For example if the input was free...

Page 6: ...f factor shift 0 AI AO 02 AO not available Sensor block diagram 6 13 www sauter controls com Bus F B10418 1 NC not connected 2 It is recommended to put the setting for forced operation for LOW voltage additionally to Vvar 3 Connection is recognised as LOW voltage and accordingly the factory setting for forced operation is performed other parameters provide different behaviour After applying power ...

Page 7: ...uitable for continuous operation After parameterisation has been completed the parameter plug must be removed and the opening should be sealed to restore the IP protection type Fitting outdoors We recommend that devices are given additional protection against the effects of weather if installed outside Wiring Power supply To ensure fault free operation the following wire cross sections and lengths...

Page 8: ...c Double earthed shielding is suitable as a protection against electromagnetic interference e g from frequency converters electric motors coils etc It is advisable to use twisted pairs Additional technical information The upper section of the housing with the lid and the lid release button contains the electronics and the sensor The lower section of the housing contains the brushless DC motor the ...

Page 9: ...ntroller 2 as standard Taking into account the logical statuses the command signal shifts the parameterised air volume values in the range from min to max With the same setting for these limitations and for the nominal air volume for the installation nom i e the parameterised values on the supply and exhaust air controllers must be the same a set point shift enables a parallel shift of the air vol...

Page 10: ...etpoint B11698 Plant schematic example 1 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 20 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V ...

Page 11: ...to the upstream pressure in the air network due to fluctuations in duct pressure control these disruptions can be detected and transmitted directly to the slave controller This guarantees an equal percentage relationship between the supply and exhaust air controllers The command signal or the actual value signal rqv from the master controller can be connected in parallel to several slave controlle...

Page 12: ... schematic example 2 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Slave exhaust air min 10 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume ac...

Page 13: ...0 m h Air volume parameters Room negative pressure supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 10 max 100 nom 1100 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume actual value master rqv 40 4 V 440 m h Printed in Switzerland Fr Sauter AG Im Surinam 55 CH 4016 Basle Tel 41 61 695 55 55 Fa...

Reviews: