background image

 

ASV115 

 

 

Logic table for digital inputs 

Configuration of connections 

Function with factory setting

 

DI05 (c

qV.p.2

) DI04 

(c

qV.p.1

var

 

min

 

max

 Damper 

closed 

 

 

n. act. 

n. act. 

n. act. act. 

act. 

n. 

act. act. 

act. 

 

 

n. act. 

act. 

n. act. 

n. 

act. 

act. act. act. n. 

act. 

  act. 

n. 

act. 

act. 

act. 

n. act. 

n. act. 

n. act. 

act. 

  act. 

act. 

act. 

n. 

act. 

n. act. 

act. 

n. act. 

n. act. 

 

n. act.= connected switch or contacts are 

not activated

, i.e. normally open contacts are open and normally closed are closed. 

act. = connected switch or contacts are 

activated

, i.e. normally open contacts are closed and normally closed are open. 

 

In order to stabilise the sensor's measurement signal in case of 
severely fluctuating pressure signals, the SAUTER CASE VAV 
software can be used to set the filter time constant 

 continuously in 

a range from 0 to 5.22 s. Zero can be reset as required by using the 
zeroing function. 

Sensor technology 

The measuring sensor used in the VAV controller is a static double-
membrane sensor manufactured using PCB technology. Thanks to 
its symmetrical structure with two measuring cells which are (in 
principle) independent, the sensor is position-compensated and 
can, therefore, be operated in any fitted position. The differential 
pressure is evaluated using the differential capacitance measure-
ment method. The unique design ensures highly accurate meas-
urement at differential pressures of up to < 1 Pa, allowing precise 
control of air volume at a differential pressure of 1 Pa. This enables 
users to set low 

min

 values for reduced mode in order to save 

energy. 

 

Power supply connection 

The drive can be operated with 24 V d.c. or a.c. Automatic connec-
tion recognition is available only in a.c. mode. In d.c. mode, the full 
nominal torque of 10 Nm is available within the specified tolerances. 

 

If the controller is operated with 24 V d.c., the following function 
differs from a.c. operation, in relation to analogue inputs AI01 and 
AI02: 

 

Thanks to the principle of using a static measuring method, the 
sensor can also be used to measure pumped media which contain 
dust or are contaminated with chemicals. 

 

Functions with 24 V d.c. 

Connec-
tion 

Para-
meterised 
function 

Circuit 
connec-
tion 

Function 
range 
0…10 V 

Function 
range 
2…10 V 

Function 
freely 
configur-
able 

AI 01 

Standard NC 

1)

 Vvar 

2)

 Damper 

closed 

3)

 

 

AI 

NC 

max. pos. shift if factor shift > 0 

AI/AO 02

AO 

not available 

 

Sensor block diagram 

 

6/13  

www.sauter-controls.com 

Bus

F

B

104

1

8

1) NC, not connected 
2) It is recommended to put the setting for forced operation for LOW voltage additionally to 

Vvar. 

3) Connection is recognised as 

LOW voltage

 and, accordingly, the factory setting for 

forced operation is performed; other parameters provide different behaviour.

 

 

After applying power, the working range of the damper drive is 
determined automatically. For this purpose, the drive approaches 
both limit stops and specifies the possible angle of rotation (factory 
setting). The initialisation procedure in the event of a power failure 
can be disabled by setting a parameter in the SAUTER CASE VAV 
software tool. 

 

The SAUTER CASE VAV software enables zeroing and setting of 
damping factors by the user as required. 
 

Sensor structure 

 

 

RS-485 / SLC interface function 

GND

Pn

Pp

Ac

Ap

An

B1

1

563

The VAV compact controller is fitted with an RS-485 interface which 
is not galvanically separated. The baud rate used is 115.2 kbps, 
which is a fixed setting. The SAUTER Local Communication (SLC) 
protocol that is used specifies the master-slave bus access proce-
dure, with a maximum of 31 devices permitted in one network seg-
ment. The 32

nd

 device is the parametering tool. The SAUTER CASE 

VAV software is used to parameterise each individual device and to 
configure the devices within the network segment. Physical access 
to the bus system is gained either via the connection in the housing 
cover or via three separate leads at the end of the cable. 

 

CASE VAV function 

The SAUTER CASE VAV software is available to parameterise the 
air volume controller. This software tool enables you to configure all 
the values required for operation via a comfortable user interface. 
The connection is made via a USB interface on the PC/laptop and 
via the jack on the drive, or via the RS-485 leads on the drive cable. 
The drive parameterisation set comprises: software, including in-
stallation and operating instructions, fitting instructions, connection 
plug, connection cable (length 1.2 m) and an interface converter for 
the PC. The software is intended for use by OEM manufacturers, 
commissioning and service technicians and experienced operators. 
The following functions are available: 

 

Key 

Pp 

Connection for higher pressure 

Pn 

Connection for lower pressure 

Ac 

Common pole flange of the differential capacitor 

Ap 

Positive pole flange 

An 

Negative pole flange 

GND Earth 

(ground) 

 

 

Summary of Contents for ASV115

Page 1: ... SLC SAUTER Local Communication protocol Easy to parameterise using the SAUTER CASE VAV software Constant air volume control using parameterisable inputs Technical description Power supply 24 V Variable end values for the differential pressure s measuring range 50 150 Pa 100 300 Pa Efficient control algorithm Output signal 0 10 V for Air volume actual value rq Air volume control deviation eq or fo...

Page 2: ...nded 7 Recommend hardness of tubes 40 Sha e g silicone 8 Connection 02 can be configured as an analogue input or analogue output using SAUTER CASE VAV software 9 Digital inputs for external potential free contacts gold plated recommended 10 The parametering tool is always one of the subscribers so a maximum of 31 devices can be linked 11 Recommended Belden 3106A Accessories Type Description 052045...

Page 3: ...switching contact 1 DI04 Factory setting FS Full scale PR Room pressure TR Room temperature Heating Cooling DN Nominal diameter c o Change over ad Index ad for additive p Index p for priority V Index V for air volume s Index s for second priority q Index q for quantity Setting the air volume The following functions are generally available to operate the air volume controller Setting ranges Functio...

Page 4: ... permitted angle of the damper Functional diagram for damper position The function can be set using Sauter CASE VAV 1 4 or higher which allows one of the following applications for the device to be selected VAV 10 001 M VAV 20 001 M or VAV 20 001 Sxi When setting the parameters for terminal AO02 using the feedback signal for the damper position it is recommended to perform an adaption using Manual...

Page 5: ...ression and upward limitation is defined by the maximum possible plant air volume damper fully open As an example the calculation and setting of the parallel setpoint shift may be performed as follows In order to obtain the value for the resultant setpoint shift as a per centage of the air volume the configuration of connection AI02 must also be taken into account For example if the input was free...

Page 6: ...f factor shift 0 AI AO 02 AO not available Sensor block diagram 6 13 www sauter controls com Bus F B10418 1 NC not connected 2 It is recommended to put the setting for forced operation for LOW voltage additionally to Vvar 3 Connection is recognised as LOW voltage and accordingly the factory setting for forced operation is performed other parameters provide different behaviour After applying power ...

Page 7: ...uitable for continuous operation After parameterisation has been completed the parameter plug must be removed and the opening should be sealed to restore the IP protection type Fitting outdoors We recommend that devices are given additional protection against the effects of weather if installed outside Wiring Power supply To ensure fault free operation the following wire cross sections and lengths...

Page 8: ...c Double earthed shielding is suitable as a protection against electromagnetic interference e g from frequency converters electric motors coils etc It is advisable to use twisted pairs Additional technical information The upper section of the housing with the lid and the lid release button contains the electronics and the sensor The lower section of the housing contains the brushless DC motor the ...

Page 9: ...ntroller 2 as standard Taking into account the logical statuses the command signal shifts the parameterised air volume values in the range from min to max With the same setting for these limitations and for the nominal air volume for the installation nom i e the parameterised values on the supply and exhaust air controllers must be the same a set point shift enables a parallel shift of the air vol...

Page 10: ...etpoint B11698 Plant schematic example 1 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 20 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V ...

Page 11: ...to the upstream pressure in the air network due to fluctuations in duct pressure control these disruptions can be detected and transmitted directly to the slave controller This guarantees an equal percentage relationship between the supply and exhaust air controllers The command signal or the actual value signal rqv from the master controller can be connected in parallel to several slave controlle...

Page 12: ... schematic example 2 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Slave exhaust air min 10 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume ac...

Page 13: ...0 m h Air volume parameters Room negative pressure supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 10 max 100 nom 1100 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume actual value master rqv 40 4 V 440 m h Printed in Switzerland Fr Sauter AG Im Surinam 55 CH 4016 Basle Tel 41 61 695 55 55 Fa...

Reviews: