background image

ASV115 

 

 

 

Connection plan 

For configuration purposes, the specifications for the air volume box 
must be loaded into the drive using SAUTER CASE VAV. The data 
below are required for this purpose as a minimum. 

Connection Colour 

coding  Function 

01 Red 

External 

command 

variable 

C

q

 0…10 V 

 0…100% 

nom

 

2 Black Setpoint 

shift 

C

q ad 

(

) 5 V ± 5 V 

 ± 15% 

 

03 Grey  Actual 

value 

R

q

 0…10 V 

 0…100% 

 

nom

 

04 Violet  Priority 

control 

min

 (activated condition) 

05 White  Priority 

control 

max

 (activated condition) 

 

Air volume specifications 

 DN 

box 

C factor 
box 

n

 

AT

 

nom

 

max

 

min

 

Unit 

mm l/s 

– 

m

3

/h 

l/s - m

3

/h l/s 

m

3

/h l/s - m

3

/h l/s 

m

3

/h 

 

 

Abbreviations and symbols 

n

 

Nominal air volume 

 

n AT

 

Nominal air volume for air terminal 

n effectiv

 

Effective nominal air volume 

 

nom

 

nominal 

in plant 

max

 

Maximum air volume 

 

mid

 Air 

volume 

between

max 

and

min

 

min

 

Minimum air volume 

 

int

 Internal 

air 

volume 

var

 

Continuous air volume, e.g. corresponding to command 
variable 0…10 V 

 

Differential pressure on the sensor in pascals 

VAV 

Variable air volume 

 

CAV 

Constant air volume 

cw 

C

lock

w

ise  

ccw 

C

ounter-

c

lock

w

ise 

r

qV

 

Actual value as per IEC 60050-351 (former) X

i

)  

c

qV.s

 

Command signal as per IEC 60050-351 (former X

s

r

 

Feedback signal for damper position as per IEC 60050-351 

 

-e

qV.s

 

Control deviation for air volume as per IEC 60050-351 

c

qV.p.ad

 

Command signal shift as per IEC 60050-351 (former 

)  

c

qV.p.2

 

Command signal as per IEC 60050-351 through switching 
contact 2 (DI05) 

c

qV.p.1

 

Command signal as per IEC 60050-351 through switching 
contact 1 (DI04) 

 

 

Factory setting 

FS 

F

ull 

s

cale  

P

R

 Room 

pressure 

T

R

 Room 

temperature 

 

 Heating 

 

Cooling  

DN 

Nominal 

diameter 

c/o 

C

hange-

o

ver  

 

 

 

 

 

ad 

Index ad for additive 

Index p for 'priority' 

 

Index V for air volume 

Index s for 'second priority' 

 

 

 

Index q for quantity 

 

 

 

 

Setting the air volume 

The following functions are generally available to operate the air volume controller. 

 

Setting ranges 

Function 

Air volume 

Maximum setting ranges 

Recommended setting ranges 

Damper closed 

Damper fully closed  

0° 

damper 

position 

min 

Minimum 

1Pa

 … 

max

 10…100% 

max

 

max 

Maximum 

1Pa

 … 

nom

 10…100% 

nom

 

mid 

Intermediate position 

max

 > 

mid

 > 

min

 10…100% 

max

 

Damper open 

Damper fully open 

 

90° damper position 

nom

 

Nominal air volume 

 

specific value, dependant on box type, air density and application 

int 

Internal setpoint 

1Pa

 … 

nom

 10…100% 

nom

 

 

Minimum and maximum air volume (

min

 and 

max

) via command signal (AI01)

The 

min

 and 

max

 values, which should be parameterised using 

software, impose an upper and a lower limit on the command signal 
c

qV.s

. The values to be set for 

min

 and 

max

 are entered as either 

percentages or absolute values. If absolute values are entered, the 
plant-specific differential pressure values in pascals are calculated 

using the equation below. Without an external command signal, the 
set 

min

 value becomes the setpoint. Minimum and maximum air 

volume values are overridden using digital inputs. In addition, the 
setpoint is dependent on the logical status of the command variable 
and the assigned forced operation. 

 

Calculation of 

min

 and 

max

 

 

 

 

www.sauter-controls.com  

3/13 

%

100

*

V

V

 

(%)

 

V

3

nom

3

min

min

















h

m

h

m

 

%

100

*

V

V

 

(%)

 

V

3

nom

3

max

max

















h

m

h

m

10V

0

Vmin

Vmax

Vnom

100%

0

V

cqV.s

B

1169

1

 

Summary of Contents for ASV115

Page 1: ... SLC SAUTER Local Communication protocol Easy to parameterise using the SAUTER CASE VAV software Constant air volume control using parameterisable inputs Technical description Power supply 24 V Variable end values for the differential pressure s measuring range 50 150 Pa 100 300 Pa Efficient control algorithm Output signal 0 10 V for Air volume actual value rq Air volume control deviation eq or fo...

Page 2: ...nded 7 Recommend hardness of tubes 40 Sha e g silicone 8 Connection 02 can be configured as an analogue input or analogue output using SAUTER CASE VAV software 9 Digital inputs for external potential free contacts gold plated recommended 10 The parametering tool is always one of the subscribers so a maximum of 31 devices can be linked 11 Recommended Belden 3106A Accessories Type Description 052045...

Page 3: ...switching contact 1 DI04 Factory setting FS Full scale PR Room pressure TR Room temperature Heating Cooling DN Nominal diameter c o Change over ad Index ad for additive p Index p for priority V Index V for air volume s Index s for second priority q Index q for quantity Setting the air volume The following functions are generally available to operate the air volume controller Setting ranges Functio...

Page 4: ... permitted angle of the damper Functional diagram for damper position The function can be set using Sauter CASE VAV 1 4 or higher which allows one of the following applications for the device to be selected VAV 10 001 M VAV 20 001 M or VAV 20 001 Sxi When setting the parameters for terminal AO02 using the feedback signal for the damper position it is recommended to perform an adaption using Manual...

Page 5: ...ression and upward limitation is defined by the maximum possible plant air volume damper fully open As an example the calculation and setting of the parallel setpoint shift may be performed as follows In order to obtain the value for the resultant setpoint shift as a per centage of the air volume the configuration of connection AI02 must also be taken into account For example if the input was free...

Page 6: ...f factor shift 0 AI AO 02 AO not available Sensor block diagram 6 13 www sauter controls com Bus F B10418 1 NC not connected 2 It is recommended to put the setting for forced operation for LOW voltage additionally to Vvar 3 Connection is recognised as LOW voltage and accordingly the factory setting for forced operation is performed other parameters provide different behaviour After applying power ...

Page 7: ...uitable for continuous operation After parameterisation has been completed the parameter plug must be removed and the opening should be sealed to restore the IP protection type Fitting outdoors We recommend that devices are given additional protection against the effects of weather if installed outside Wiring Power supply To ensure fault free operation the following wire cross sections and lengths...

Page 8: ...c Double earthed shielding is suitable as a protection against electromagnetic interference e g from frequency converters electric motors coils etc It is advisable to use twisted pairs Additional technical information The upper section of the housing with the lid and the lid release button contains the electronics and the sensor The lower section of the housing contains the brushless DC motor the ...

Page 9: ...ntroller 2 as standard Taking into account the logical statuses the command signal shifts the parameterised air volume values in the range from min to max With the same setting for these limitations and for the nominal air volume for the installation nom i e the parameterised values on the supply and exhaust air controllers must be the same a set point shift enables a parallel shift of the air vol...

Page 10: ...etpoint B11698 Plant schematic example 1 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 20 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V ...

Page 11: ...to the upstream pressure in the air network due to fluctuations in duct pressure control these disruptions can be detected and transmitted directly to the slave controller This guarantees an equal percentage relationship between the supply and exhaust air controllers The command signal or the actual value signal rqv from the master controller can be connected in parallel to several slave controlle...

Page 12: ... schematic example 2 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Slave exhaust air min 10 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume ac...

Page 13: ...0 m h Air volume parameters Room negative pressure supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 10 max 100 nom 1100 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume actual value master rqv 40 4 V 440 m h Printed in Switzerland Fr Sauter AG Im Surinam 55 CH 4016 Basle Tel 41 61 695 55 55 Fa...

Reviews: