ASV115
Connection plan
For configuration purposes, the specifications for the air volume box
must be loaded into the drive using SAUTER CASE VAV. The data
below are required for this purpose as a minimum.
Connection Colour
coding Function
01 Red
External
command
variable
C
q
0…10 V
0…100%
nom
2 Black Setpoint
shift
C
q ad
(
) 5 V ± 5 V
± 15%
03 Grey Actual
value
R
q
0…10 V
0…100%
nom
04 Violet Priority
control
min
(activated condition)
05 White Priority
control
max
(activated condition)
Air volume specifications
DN
box
C factor
box
n
AT
nom
max
min
Unit
mm l/s
–
m
3
/h
l/s - m
3
/h l/s
-
m
3
/h l/s - m
3
/h l/s
-
m
3
/h
Abbreviations and symbols
n
Nominal air volume
n AT
Nominal air volume for air terminal
n effectiv
Effective nominal air volume
nom
nominal
in plant
max
Maximum air volume
mid
Air
volume
between
max
and
min
min
Minimum air volume
int
Internal
air
volume
var
Continuous air volume, e.g. corresponding to command
variable 0…10 V
p
Differential pressure on the sensor in pascals
VAV
Variable air volume
CAV
Constant air volume
cw
C
lock
w
ise
ccw
C
ounter-
c
lock
w
ise
r
qV
Actual value as per IEC 60050-351 (former) X
i
)
c
qV.s
Command signal as per IEC 60050-351 (former X
s
)
r
Feedback signal for damper position as per IEC 60050-351
-e
qV.s
Control deviation for air volume as per IEC 60050-351
c
qV.p.ad
Command signal shift as per IEC 60050-351 (former
)
c
qV.p.2
Command signal as per IEC 60050-351 through switching
contact 2 (DI05)
c
qV.p.1
Command signal as per IEC 60050-351 through switching
contact 1 (DI04)
Factory setting
FS
F
ull
s
cale
P
R
Room
pressure
T
R
Room
temperature
Heating
Cooling
DN
Nominal
diameter
c/o
C
hange-
o
ver
ad
Index ad for additive
p
Index p for 'priority'
V
Index V for air volume
s
Index s for 'second priority'
q
Index q for quantity
Setting the air volume
The following functions are generally available to operate the air volume controller.
Setting ranges
Function
Air volume
Maximum setting ranges
Recommended setting ranges
Damper closed
Damper fully closed
0°
damper
position
min
Minimum
1Pa
…
max
10…100%
max
max
Maximum
1Pa
…
nom
10…100%
nom
mid
Intermediate position
max
>
mid
>
min
10…100%
max
Damper open
Damper fully open
90° damper position
nom
Nominal air volume
specific value, dependant on box type, air density and application
int
Internal setpoint
1Pa
…
nom
10…100%
nom
Minimum and maximum air volume (
min
and
max
) via command signal (AI01)
The
min
and
max
values, which should be parameterised using
software, impose an upper and a lower limit on the command signal
c
qV.s
. The values to be set for
min
and
max
are entered as either
percentages or absolute values. If absolute values are entered, the
plant-specific differential pressure values in pascals are calculated
using the equation below. Without an external command signal, the
set
min
value becomes the setpoint. Minimum and maximum air
volume values are overridden using digital inputs. In addition, the
setpoint is dependent on the logical status of the command variable
and the assigned forced operation.
Calculation of
min
and
max
www.sauter-controls.com
3/13
%
100
*
V
V
(%)
V
3
nom
3
min
min
h
m
h
m
%
100
*
V
V
(%)
V
3
nom
3
max
max
h
m
h
m
10V
0
Vmin
Vmax
Vnom
100%
0
V
cqV.s
B
1169
1