ASV115
Technical data
(continued)
p
sensor
(continued)
Interfaces, communication
(continued)
Influence of position
± 1 Pa
Length of cable
Reproducibility
0.2% FS
without bus termination
up to 200 m, Ø 0.5 mm
Zero point stability at 20 C
0.2% FS
with bus termination
up to 500 m, Ø 0.5 mm
Permitted positive pressure
± 10 kPa
Cable type
twisted pair
11)
Permitted operating pressure p
stat
± 3 kPa
6)
Bus termination
> 200 m, 120
both sides
Air connection
Ø i = 3.5...6 mm
7)
Permitted ambient conditions
Inputs
Operating temperature
0…55 °C
AI01 analogue
0…10 V (R
i
= 100 k
)
Storage and transport temperature
-20…55 °C
AI02 analogue
8)
0…10
V
(R
i
= 70 k
)
Humidity
<
85%
rh
DI04 digital
9)
closed < 0.5 V, 1.3 mA
no condensation
open > 2 V~
DI05 digital
9)
closed < 0.5 V~, 1 mA
Installation
open > 3 V ~
Weight (kg)
0.8
Outputs
Standards, guidelines and directives
AO03 analogue
0…10 V load > 10 k
Type of protection (horizontal)
IP 54 (EN 60529)
AO02 Analogue
8)
0…10 V load > 10 k
Protection class
III (EN 60730)
Degree of contamination
2 (EN 60730)
Interfaces, communication
RS-485 not galv. separated
115 kBaud
Additional information
Protocol
SAUTER Local Communication (SLC)
Fitting instructions
MV 506011
Access method
Master/slave
CASE VAV manual
7010022001
Topology
Line
Material declaration
MD 52.100
Number of subscribers
31/32
10)
diagram
1) Holding torque (not under power) due to self-locking in transmission system 1 Nm
2) Non-connected analogue inputs are valued at 0 V. The nominal torque is attained within the given tolerances. AI/AO can be used only as an input.
3) Holding torque > 10 Nm
4) Running time can be set via the software
5) Maximum angle of rotation 95° (without end stop)
6) Brief overload; the sensor's zero-point adjustment is recommended
7) Recommend hardness of tubes < 40 Sha (e.g. silicone)
8) Connection 02 can be configured as an analogue input or analogue output using SAUTER CASE VAV software
9) Digital inputs for external potential-free contacts (gold-plated recommended)
10) The parametering tool is always one of the subscribers, so a maximum of 31 devices can be linked
11) Recommended: Belden 3106A
Accessories
Type
Description
0520450010*
CASE VAV – USB connection set, incl. software
CERTIFICAT001 Manufacturer’s test certificate type M including
p sensor calibration data
0372300001
Anti-torsion device, long (230 mm)
0372301001
Shaft adaptor for squared end (x 15 mm) hollow profile (pack of 10)
XAFP100F001*
Dynamic-pressure sensor for measuring air volumes in ventilation ducts
*) Dimension drawing or wiring diagram is available under the same number
General description of operation
The differential pressure created on an orifice plate or a dynamic
pressure sensor is recorded by a static differential pressure sensor
and is converted into a flow-linear signal. An external command
signal c
q
is limited by the parameterised minimum and maximum
settings, and is compared with the actual air volume r
q
. Based on
the control deviation that is determined, the damper on the air
volume box is adjusted by the drive until the required air volume is
attained over the measurement point. Without an external com-
mand signal, the value for
min
that was specified in the parame-
terisation corresponds to command variable c
q
Configuration of the
application and the internal parameters is software-based, using
SAUTER CASE VAV PC software.
The software supports the application-specific configuration of the
compact controller and the setting of the necessary parameters in
bus mode. The VAV compact controller is supplied ex factory with a
standard configuration. For this purpose, the inputs and outputs are
preconfigured as shown in the table.
2/13
www.sauter-controls.com