background image

 

ASV115 

 

Technical data 

(continued)

 

p

 

sensor 

(continued)

 

 

 

Interfaces, communication 

(continued)

 

 

Influence of position 

± 1 Pa 

 

Length of cable 

 

Reproducibility 

0.2% FS 

 

without bus termination 

up to 200 m, Ø 0.5 mm 

Zero point stability at 20 C 

0.2% FS 

 

with bus termination 

up to 500 m, Ø 0.5 mm 

Permitted positive pressure 

± 10 kPa  

 

Cable type 

twisted pair 

11)

 

Permitted operating pressure p

stat

 

± 3 kPa 

6)

 

 

Bus termination 

> 200 m, 120 

 both sides 

Air connection 

Ø i = 3.5...6 mm 

7)

 

 

 

 

 

 

 

Permitted ambient conditions 

 

Inputs 

 

 

Operating temperature 

0…55 °C 

AI01 analogue 

0…10 V (R

i

 = 100 k

 

Storage and transport temperature 

-20…55 °C 

AI02 analogue

 8)

 0…10 

(R

i

 = 70 k

)  

Humidity 

85% 

rh 

DI04 digital 

9)

 

closed < 0.5 V, 1.3 mA 

 

 

no condensation 

 

open > 2 V~ 

 

 

 

DI05 digital 

9)

 

closed < 0.5 V~, 1 mA 

 

Installation 

 

 

open > 3 V ~ 

 

Weight (kg) 

0.8 

 

 

 

 

 

Outputs 

 

 

Standards, guidelines and directives

 

AO03 analogue 

0…10 V load > 10 k

 

 

Type of protection (horizontal) 

IP 54 (EN 60529) 

AO02 Analogue 

8)

 

0…10 V load > 10 k

 

 

Protection class 

III (EN 60730) 

 

 

 

Degree of contamination 

2 (EN 60730) 

Interfaces, communication 

 

 

 

 

RS-485 not galv. separated 

115 kBaud 

 

Additional information 

 

Protocol 

SAUTER Local Communication (SLC)  

Fitting instructions 

MV 506011 

Access method 

Master/slave 

 

CASE VAV manual 

7010022001 

Topology 

Line 

 

Material declaration 

MD 52.100 

Number of subscribers 

31/32 

10)

 

 

 

 

   

Dimension 

drawing 

M10457

 

  

 

Wiring 

diagram 

A10519

 

1) Holding torque (not under power) due to self-locking in transmission system 1 Nm 

2) Non-connected analogue inputs are valued at 0 V. The nominal torque is attained within the given tolerances. AI/AO can be used only as an input. 

3) Holding torque > 10 Nm 

4) Running time can be set via the software 

5) Maximum angle of rotation 95° (without end stop) 

6) Brief overload; the sensor's zero-point adjustment is recommended 

7) Recommend hardness of tubes < 40 Sha (e.g. silicone) 

8) Connection 02 can be configured as an analogue input or analogue output using SAUTER CASE VAV software 

9) Digital inputs for external potential-free contacts (gold-plated recommended) 

10) The parametering tool is always one of the subscribers, so a maximum of 31 devices can be linked 

11) Recommended: Belden 3106A 

Accessories 

Type 

Description 

0520450010* 

CASE VAV – USB connection set, incl. software 

CERTIFICAT001  Manufacturer’s test certificate type M including 

p sensor calibration data 

0372300001 

Anti-torsion device, long (230 mm) 

0372301001 

Shaft adaptor for squared end (x 15 mm) hollow profile (pack of 10) 

XAFP100F001* 

Dynamic-pressure sensor for measuring air volumes in ventilation ducts 

*) Dimension drawing or wiring diagram is available under the same number 

 

General description of operation 

The differential pressure created on an orifice plate or a dynamic 
pressure sensor is recorded by a static differential pressure sensor 
and is converted into a flow-linear signal. An external command 
signal c

q

 is limited by the parameterised minimum and maximum 

settings, and is compared with the actual air volume r

q

. Based on 

the control deviation that is determined, the damper on the air 
volume box is adjusted by the drive until the required air volume is 
attained over the measurement point. Without an external com-
mand signal, the value for 

min

 that was specified in the parame-

terisation corresponds to command variable c

q

 Configuration of the 

application and the internal parameters is software-based, using 
SAUTER CASE VAV PC software.  

 

The software supports the application-specific configuration of the 
compact controller and the setting of the necessary parameters in 
bus mode. The VAV compact controller is supplied ex factory with a 
standard configuration. For this purpose, the inputs and outputs are 
preconfigured as shown in the table. 

2/13  

www.sauter-controls.com 

Summary of Contents for ASV115

Page 1: ... SLC SAUTER Local Communication protocol Easy to parameterise using the SAUTER CASE VAV software Constant air volume control using parameterisable inputs Technical description Power supply 24 V Variable end values for the differential pressure s measuring range 50 150 Pa 100 300 Pa Efficient control algorithm Output signal 0 10 V for Air volume actual value rq Air volume control deviation eq or fo...

Page 2: ...nded 7 Recommend hardness of tubes 40 Sha e g silicone 8 Connection 02 can be configured as an analogue input or analogue output using SAUTER CASE VAV software 9 Digital inputs for external potential free contacts gold plated recommended 10 The parametering tool is always one of the subscribers so a maximum of 31 devices can be linked 11 Recommended Belden 3106A Accessories Type Description 052045...

Page 3: ...switching contact 1 DI04 Factory setting FS Full scale PR Room pressure TR Room temperature Heating Cooling DN Nominal diameter c o Change over ad Index ad for additive p Index p for priority V Index V for air volume s Index s for second priority q Index q for quantity Setting the air volume The following functions are generally available to operate the air volume controller Setting ranges Functio...

Page 4: ... permitted angle of the damper Functional diagram for damper position The function can be set using Sauter CASE VAV 1 4 or higher which allows one of the following applications for the device to be selected VAV 10 001 M VAV 20 001 M or VAV 20 001 Sxi When setting the parameters for terminal AO02 using the feedback signal for the damper position it is recommended to perform an adaption using Manual...

Page 5: ...ression and upward limitation is defined by the maximum possible plant air volume damper fully open As an example the calculation and setting of the parallel setpoint shift may be performed as follows In order to obtain the value for the resultant setpoint shift as a per centage of the air volume the configuration of connection AI02 must also be taken into account For example if the input was free...

Page 6: ...f factor shift 0 AI AO 02 AO not available Sensor block diagram 6 13 www sauter controls com Bus F B10418 1 NC not connected 2 It is recommended to put the setting for forced operation for LOW voltage additionally to Vvar 3 Connection is recognised as LOW voltage and accordingly the factory setting for forced operation is performed other parameters provide different behaviour After applying power ...

Page 7: ...uitable for continuous operation After parameterisation has been completed the parameter plug must be removed and the opening should be sealed to restore the IP protection type Fitting outdoors We recommend that devices are given additional protection against the effects of weather if installed outside Wiring Power supply To ensure fault free operation the following wire cross sections and lengths...

Page 8: ...c Double earthed shielding is suitable as a protection against electromagnetic interference e g from frequency converters electric motors coils etc It is advisable to use twisted pairs Additional technical information The upper section of the housing with the lid and the lid release button contains the electronics and the sensor The lower section of the housing contains the brushless DC motor the ...

Page 9: ...ntroller 2 as standard Taking into account the logical statuses the command signal shifts the parameterised air volume values in the range from min to max With the same setting for these limitations and for the nominal air volume for the installation nom i e the parameterised values on the supply and exhaust air controllers must be the same a set point shift enables a parallel shift of the air vol...

Page 10: ...etpoint B11698 Plant schematic example 1 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 20 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V ...

Page 11: ...to the upstream pressure in the air network due to fluctuations in duct pressure control these disruptions can be detected and transmitted directly to the slave controller This guarantees an equal percentage relationship between the supply and exhaust air controllers The command signal or the actual value signal rqv from the master controller can be connected in parallel to several slave controlle...

Page 12: ... schematic example 2 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Slave exhaust air min 10 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume ac...

Page 13: ...0 m h Air volume parameters Room negative pressure supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 10 max 100 nom 1100 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume actual value master rqv 40 4 V 440 m h Printed in Switzerland Fr Sauter AG Im Surinam 55 CH 4016 Basle Tel 41 61 695 55 55 Fa...

Reviews: