24
www.cranecpe.com
Crane ChemPharma & Energy
Default Factory Settings and EDS Options
The Eletronic Data Sheet (EDS) file is an electronic file that describes the operating and configuration parameters of the equipment,
and is distributed by the manufacturer
The EDS file allows configuration of features and parameters at the master PLC or DCS.
The EDS parameters are outlined below:
DeviceNet
Communication Bytes
Input
Byte
Input Bits
Meaning
7
6
5
4
3
2
1
0
1
0
0
Valve in Mid-Stroke Position
0
1
Valve Closed
1
0
Valve Open
1
1
Not Used
1
Solenoid is Forced (at Sensor)
1
Self Calibration Status (1=Failed)
0
Asking PLC
1
to Power External Solenoid OFF
1
Asking PLC
1
to Power External Solenoid ON
1
General Alarms
X
Not Used
X
Not Used
Communication Bytes
Output Byte
Output Bits
7
6
5
4
3
2
1
0
1
Factory Reset
Self Calibration
Solenoid
Command
ID
Parameter
Current Value
1
Self Calibration
YES, NO
2
Self Calibration Confirm.
OK, FAIL
3
Factory Reset
YES, NO
Note 1: Use with external solenoid in self calibration mode.
Note 2: To use with external solenoid during Self Calibration Mode.
Note 3: The input bits in this table are factory default settings. If the output option is switched from nC to nO the input bit 1 and
input bit 0 will be inverted. For more information see “Switching Output Options.”
Note: In order to perform a successful calibration after 3 seconds Output Bit 2 must be changed from 1 to 0, otherwise the system will not
self-calibrate.
Visit www.SaundersM-VUE.com
for the latest EDS files.