28
www.cranecpe.com
Crane ChemPharma & Energy
Using the M-VUE Menus
Hold the magnetic key over H2 for 3
seconds . The ring of LED’s will flash
green for 2 seconds (this indicates
Configuration Mode has been accessed)
3 sec. to confirm hand calibration
To exit the configuration mode
hold the magnetic key over H1 for
more than 3 seconds or wait 30 seconds
without approaching any magnetic key
to either H1 or H2 buttons
All LEDs will flash for 2 seconds immediately
after P1 will flash green. Use H1 to select
• P6: Factory Reset
Restore Factory Settings
The Main Menu is accessed via the
magnetic buttons H1 and H2 and is used
to calibrate and program the sensor.
Setting Network Speed/Baud Rate (DeviceNet Units Only)
This parameter allows the data rate to be selected. The M-VUE can communicate data at
a rate of 125, 250 or 500 Kbit/s (MVUE’s default Baud Rate is 125 Kbits/s)
IMPORTANT!
The
communication rate must be set to be the same one used in other network equipment.
3 sec. to confirm factory reset
Once P6 has been selected hold the
magnetic key over H2 for 3 seconds.
All LEDs will flash green for 2 seconds
indicating the sensor has been reset to
factory settings.
Hold the magnetic key over H2
for 3 seconds. The ring of LED’s
will flash green for 2 seconds.
(This indicates Configuration
Mode has been accessed.)
All LEDs will flash for 2 seconds
immediately after P1 will flash
green. Use H1 to select SET on the
LCD screen
• P2 and P5 LEDs will flash green
Once P3 has been selected hold
the magnetic key over H2 to access
the two available options and use
H1 to select the desired option:
• P3 LED lights red and green:
integrated solenoid option.
• P3 LED light green: external or
remote solenoid option
Use H1 to select the desired
rate. (125, 250 or 500)
Use H2 to confirm the
desired numeric value.
After the “units “digit has been set, the “TENs” digit will flash (waiting to
change or confirm the current value)
To exit the configuration mode hold the magnetic key over H1 for more than 3 seconds.
Note: Baud Rate configuration of MVUE can also be performed remotely during valve
commission form the control system (DCS or PLC)