12
Calibration
Feature
P2P
AS-Interface
DeviceNet
Integral Solenoid Remote Solenoid Integral Solenoid Remote Solenoid Integral Solenoid Remote Solenoid
Self-
Calibration
At the sensor (Locally)
Yes
No
Yes
Yes
Yes
Yes
Remote (DCS or PLC)
No
No
Yes
Yes
Yes
Yes
Address Device
At the sensor (Locally)
No
No
No
No
Yes
Yes
Remote (DCS or PLC)
No
No
Yes
Yes
Yes
Yes
Programming
M-VUE
At the sensor (Locally)
Yes
Yes
Yes
Yes
Yes
Yes
Remote (DCS or PLC)
No
No
Yes
Yes
Yes
Yes
Alarm
Diagnostics
At the sensor (Locally)
Yes
Yes
Yes
Yes
Yes
Yes
Remote (DCS or PLC)
No
No
Yes
Yes
Yes
Yes
Calibration and Setting Options
The features of M-VUE are dependent on both the network/communication protocol
and the use of integral or remote solenoid.
The table below outlines the possibilities of each of the M-VUE network protocols
Description of LEDs
LED Functions:
• P1: Self Calibration
• P2: Hand Calibration
• P3: Solenoid Option
• P4: Output Inversion
• P5: Led Inversion
• P6: Factory Reset
• H1 Led: Light blue
(when magnetic key is present)
• H2 Led: Light blue
(when magnetic key is present)
• Power Led:
• Light green when power is applied
to sensor
• AS-Interface and DeviceNet versions:
• Blinking green: Not allocated
• Light red: No communication
established
• Blinking green/red: Peripheral failure
www.cranecpe.com
Crane ChemPharma & Energy