14
www.cranecpe.com
Crane ChemPharma & Energy
1. Hold the magnetic key over H2 for 3 seconds . The ring of LED’s will flash green for 2 seconds (this indicates Configuration
Mode has been accessed)
2. Hold the magnetic key over H1 to select the Hand Calibration Mode (P2 LED must be flashing)
3. Confirm the selection of P2 by holding the magnetic key over H2 for 3 seconds
4. P2 LED will light red. This is indication that the aseptic valve is in the CLOSED position. Confirm the CLOSED position by holding
the magnetic key over H2
5. P2 LED will light green. This is indication that the aseptic valve needs to be OPEN position. Confirm the OPEN position with the
magnetic key over H2.
6. To exit the configuration mode hold the magnetic key over H1 for more than 3 seconds or wait 30 seconds without
approaching any magnetic key to either H1 or H2 buttons
Hand-Calibration
Remote Solenoid
Asking for Open
3 Seconds to Confirm
Hand Calibration
Asking for Close