background image

CONN

E

CT

IO

N

 

Dataloggers SenNet DL150 / DL151 / DL170 / DL171 / DL172. Technical manual

 

42

 

Satel Spain 

 

Version 1.01

 

8.

 

CONNECTION OF THE DL172 

 

8.1.

 

Connection to the power supply 

 
The same instructions as for the DL170 model should be followed (see section 6.1 Connection to the 
power supply, 
p. 37). 
 

8.2.

 

Connection of the antennas: GPRS/3G, Z-Wave (optional) and RF 

 
The terminal of the radio frequency antenna is SMA (Sub Miniature version A). You should verify which 
antenna corresponds to RF and which to GPRS. All dataloggers DL172 have RF and GPRS outputs. 
 

 

The  RF  antenna  should  be  installed  following  the  ESD  protections  to 
prevent damage to the device

 

 
There are two LED lights that show the status of the RF module. If the radio is active, the bottom LED 
will be on. The upper LED will blink whenever the datalogger makes a shipment by RF 
 

8.3.

 

Ethernet port connection 

 
The Ethernet port is in the opposite side to the terminals. 

8.4.

 

GSM/GPRS port connection 

 
The slot for the SIM card is located in the lower right part. A SIM card is needed for the GSM/GPRS 
communications. There is a second slot for the µSD card.  
  
The terminals of the radio frequency and Z-Wave antennas are SMA (Sub Miniature version A). You 
should verify which antenna corresponds to RF and which to GPRS. 
 

 

The GSM/GPRS antenna should be installed following the ESD protections 
to prevent damage to the device 

 

8.5.

 

Digital outputs connection 

 
The  same  instructions  as  for  the  DL170  model  should  be  followed  (see  section  6.6  Digital  outputs 
connection,
 p. 38). 
 

8.6.

 

Connection of the electricity meters 

 
The model DL172 incorporates six internal 3-phase electricity meters. There are three meters in each 
row, each one, with 6 terminals to measure the current (intensity). In addition, in each row there are 4 
terminals for the voltage reference (VN, V1, V2 and V3). The same instructions as for the DL151 model 
should be followed see section 5.5 Connection of the electricity meters, p. 26)
 

Summary of Contents for SENNET DL150

Page 1: ...Dataloggers series Device network DL150 DL151 DL170 DL171 DL172 ...

Page 2: ...CONTENIDO CONTENT Dataloggers SenNet DL150 DL151 DL170 DL171 DL172 Technical Manual Version 1 01 Satel Spain 2 CONTENT ...

Page 3: ...e 16 3 6 3 Frequency 16 3 6 4 Current intensity 16 3 6 5 Precision 17 3 6 6 Indicators 17 3 6 7 Calculation of the active and the reactive power 17 3 6 8 Power Quality 17 3 7 DL 150 Technical specifications 18 3 8 DL 151 Technical specifications 19 3 9 DL 170 Technical specifications 20 3 10 DL 171 Technical specifications 21 3 11 DL 172 Technical specifications 22 CONNECTION OF THE DATALOGGER 23 ...

Page 4: ...t connection 38 6 5 GSM GPRS port connection 38 6 6 Digital outputs connection 38 6 7 RS485 port connection 39 7 Connection of the DL 171 41 7 1 Connection to the power supply 41 7 2 Connection of the antennas GPRS 3G Z Wave optional and RF 41 7 3 USB Wi Fi port connection 41 7 4 Ethernet port connection 41 7 5 GSM GPRS port connection 41 7 6 Digital outputs connection 41 7 7 Connection of the ele...

Page 5: ...5 15 4 Router 65 15 5 Actions 65 15 6 Dyn DNS 67 15 7 Platform params 67 15 7 1 Carriots 68 15 7 2 SenNet API 69 15 7 3 Sofia2 credentials 71 15 7 4 Flythings 72 15 8 Change password 72 15 9 Save changes 72 16 Access to data through Modbus TCP 73 16 1 Datalogger s data 73 16 2 Device s data 74 16 2 1 Common to all devices 74 16 2 2 Device specific data 74 17 Access to data through XML 75 17 1 vers...

Page 6: ...rt screen to access to the datalogger s interface the screen may slightly vary depending on the model and type of license 46 Figure 21 Interface menus 47 Figure 22 Menu Access data captured overview 48 Figure 23 Overview of the menu digital inputs 49 Figure 24 Overview of the menu Outputs In this case the digital outputs DO1 DO2 and DO4 are enabled green and DO3 is disabled red 49 Figure 25 Overvi...

Page 7: ...grator s specifications 68 Figure 44 Overview of the menu Configuration General parameters to configure Sofia 2 71 Figure 45 Overview of the Loggercontrol programme 82 Figure 46 Example of configuration of three meters one three phase one single phase and another one three phase with Rogowski Path Configuration Application parameters 83 Figure 47 Example of real time monitoring with Real Time Seri...

Page 8: ......

Page 9: ...CONTENIDO WARNINGS Manual Datalogger SenNet DL150 DL151 DL170 DL171 DL172 Version 1 01 Satel Spain 9 WARNINGS ...

Page 10: ... electricity in your country The wires installed in the electrical panels must be bridled and if possible fastened to the frame and away from the bus bar Always use the required personal protective equipment At least without prejudice to the applicable law to install equipment in the electrical panels the technician must be equipped with goggles gloves and boots approved for working on electrical ...

Page 11: ...CHARACTERISTICS Manual Datalogger SenNet DL150 DL151 DL170 DL171 DL172 Version 1 01 Satel Spain 11 CHARACTERISTICS ...

Page 12: ...the objective is to provide an open and versatile solution able to connect with third party devices regardless of the mark or model Compatibility with management software SenNet dataloggers can operate with a large number of management platforms thanks to the number of standard communication mechanisms supported by the device such as o Sending files in CSV format via FTP o Sending files in XML for...

Page 13: ...C SO memory 2 GB 4 GB Card slot micro SD form memory expansion Internal battery up to 45 min RTC real time clock Internal energy meters Active and reactive energy power power factor current voltage surges power cuts 3 three phase or 9 single phase 3 three phase or 9 single phase 6 three phase or 9 single phase Inputs and outputs Current output 5V 300mA Standard output VinpUT 100mA 4 4 4 Standard i...

Page 14: ...ted 3 2 Access to captured data The data captured by the datalogger can be remotely obtained via Integrated GPRS module only in models DL170 DL171 and DL172 Optional 3G module available for models DL170 DL171 and DL172 External router connected to the Ethernet port Wi Fi models DL150 DL151 DL170 DL171 HDMI models DL150 DL151 DL170 DL171 The mechanisms offered by the datalogger to access the data c...

Page 15: ...0 DL171 and DL172 MESH wireless network 10mW and SMA connector for antennas The datalogger coordinates the network master As standard the radio is set to work at 868 MHz open frequency in the European Union however it can be configured to work at 915 MHz for most countries in America or 784 MHz most countries in Asia The dataloggers can connect via radio with a network of metering devices o Gatewa...

Page 16: ...actor cos phi o Power active reactive apparent o Energy active reactive apparent For the three phases as a whole o Power active reactive apparent o Energy active reactive apparent Frequency Power failure detection voltage drops or interruptions Voltage peaks detection 3 6 1 Measurement options DL151 and DL171 models Up to 3 three phase circuits or up to 9 single phase circuits Maximum permitted co...

Page 17: ...power and consequently for calculating the active and reactive energy They use a DSP Digital Signal Processor that makes the calculations for the entire range of fundamentals and harmonics Calculation of the active power 𝑉𝑘𝑉𝑘 cos 𝜑𝑘 𝑌𝑘 𝑘 1 Calculation of the reactive power 𝑉𝑘𝑉𝑘 sin 𝜑𝑘 𝑌𝑘 𝑘 1 Where k goes from 1 fundamental value through all the harmonics 2 3 3 6 8 Power Quality The internal electr...

Page 18: ... 3 8 13 ARM Cortex A 8 based core 600 MHz to 1 GHz RAM memory 512MB internal eMMC 2GB 4GB Memory expansion not included micro SD 4 GB optional not removable Required for the use of the embedded platform All In One Battery Internal backup battery 45 min approx RTC Real time clock Radio Frequency SenNet RF 868MHz optional Zwave optional Sizes 116x106x63 mm with terminals Weight approx 400 g with ter...

Page 19: ... included micro SD 4 GB optional not removable Required for the use of the embedded platform All In One Battery Internal backup battery 45 min approx RTC Real time clock Radio Frequency SenNet RF 868MHz optional Zwave optional Internal electricity meters x3 Internal 3 phase meters for CT 0 33 Vac or Rogowski coils Voltage meters for each phase Energy active reactive apparent Power active reactive ...

Page 20: ...ndard output Vinput 100 mA x4 standard input Operating system processors Linux 3 8 13 ARM Cortex A 8 based core 600 MHz to 1 GHz RAM memory 512MB Internal eMMC 2GB 4GB Memory expansion not included External micro SD Required for the use of the embedded platform All In One Battery Internal backup battery 45 min approx RTC Real time clock Radio Frequency SenNet RF 868MHz Zwave optional Sizes 116x106...

Page 21: ...e 600 MHz to 1 GHz RAM memory 512MB Internal eMMC 2GB 4GB Memory expansion not included External micro SD Required for the use of the embedded platform All In One Battery Internal backup battery 45 min approx RTC Real time clock Radio Frequency SenNet RF 868MHz Zwave optional Internal electricity meters x3 Internal 3 phase meters for CT 0 33 Vac or Rogowski coils Voltage meters for each phase Ener...

Page 22: ... 1 GHz RAM memory 512MB Internal eMMC 2GB 4GB Memory expansion not included External micro SD Required for the use of the embedded platform All In One Battery Internal backup battery 45 min approx RTC Real time clock Radio Frequency SenNet RF 868MHz Internal electricity meters x3 Internal 3 phase meters for CT 0 33 Vac or Rogowski coils Voltage meters for each phase Energy active reactive apparent...

Page 23: ...CONNECTION Dataloggers SenNet DL150 DL151 DL170 DL171 DL172 Technical manual Version 1 01 Satel Spain 23 CONNECTION OF THE DATALOGGER ...

Page 24: ...you a suitable power supply For greater safety it is recommended to use a 2A fuse in the power supply line Terminals Description Figure 7 Terminals Power supply ground and RS485 port 1 Power supply 5 VDC the use of a 2Afuse is recommended 2 3 A RS485 port 4 B 4 2 Connection of the RF and Z Wave antennas both optional The terminals of the radio frequency and Z Wave antennas are SMA Sub Miniature ve...

Page 25: ...sion 1 01 Satel Spain 25 4 4 Ethernet port connection The Ethernet port is on the side of the terminals and the power supply 4 5 RS485 port connection The terminals of the RS485 port are located next to the power supply terminals See Figure 7 Terminals Power supply ground and RS485 ...

Page 26: ... connection The Ethernet port is on the side of the terminals and the power supply 5 5 Connection of the electricity meters The personnel involved in the installation must be properly trained and authorized to act according to the Electrical Code and the regulations on electricity in your country To verify that the correct connection of the device please follow the ABC method explained in section ...

Page 27: ...e In single phase systems this step is not required The phases must be identified with the help of a phase meter knowing that in Europe between phase and neutral the voltage must be 220 V and between two phases there should be 380 V 3 In case you want to install submeters for example for lighting A C or other parts of the plant you must also identify the phases to which the meter is connected whet...

Page 28: ...olution of active reactive and apparent power in real time Opposite to the terminals there is a LED display for each phase 5 5 2 Configuration as 3 three phase meters The instrument can meter the consumption of 3 three phase circuits named T1 T2 and T3 For the purpose of this manual the three phase meters have the following id s T1 id 1 T2 id 2 T3 id 3 The reference voltage is common to the three ...

Page 29: ...igure 9 Terminals 1 22 of the electricity meters 5 5 3 Configuration as 9 single phase meters When used to measure single phase circuits the instrument can capture consumption data of 9 single phase circuits with the designation M11 M12 M13 M21 M22 M23 M31 M32 M33 For the purpose of this manual the single phase meters have the following id s M11 id 11 M12 id 12 M13 id 13 M21 id 21 M22 id 22 M23 id...

Page 30: ... DL171 DL172 Technical manual 30 Satel Spain Version 1 01 Figure 10 Example Connection of a three phase electricity meter GENERAL Rogowski coils 200A 500A 200 5000 A Rogowski coils can be used OR ALSO 5 1500 A current transformers GENERAL ...

Page 31: ...ataloggers SenNet DL150 DL151 DL170 DL171 DL172 Technical manual Version 1 01 Satel Spain 31 Figure 11 Example Connection of 3 three phase electricity meters GENERAL Split core CT s 5 800 A A C LIGHTING ...

Page 32: ...anual 32 Satel Spain Version 1 01 Figure 12 Example Connection of 2 three phase meters and 3 single phase The single phase meter must be connected to different phases R S or T GENERAL Split core CT S 5 800 A LIGHTING FLOOR 2 LIGHTING FLOOR1 LIGHTING OUTDOORS A C ...

Page 33: ...0 DL151 DL170 DL171 DL172 Technical manual Version 1 01 Satel Spain 33 Figure 13 Example Connection of 3 three phase meters and a meter from the utility company via RS232 or RS485 serial port GENERAL A C LIGHTING RS232 RS485 ...

Page 34: ... M13 Group 2 M21 M22 M23 Group 3 M31 M32 M33 SP1 1 SP1 2 SP1 3 SP2 1 SP2 2 SP2 3 SP3 1 SP3 2 SP3 3 Voltage reference I I I 2 I I I I I 2 I I I I I 2 I I VN V1 V2 V3 Figure 14 Example Connection of three single phase electricity meters to the current and voltage references 5 5 4 Configuration as a combination of three phase and single phase meters Apart from the configuration as 3 three phase or ni...

Page 35: ...It is important to note that the single phase meters M11 M21 and M31 are associated with the V1 phase the single phase meters M12 M22 and M32 to the V2 phase and M13 M23 and M33 to the V3 phase For example in this case M13 is associated with V3 so the current transformer or Rogowski coil must be installed on V3 In the following diagram there is an example in which only T2 and M13 are used SP1 3 Th...

Page 36: ...00A o 150A o 400A o 800A o 1500A o Connection of the CT s Black negative White positive Rogowski coils for rated currents up to 5000A It is recommended for currents between 100A and 5000A Never use these type of coils for loads with rated currents lower than 5A Connection to the terminals Black wire to the negative terminal Red wire to the positive one The arrow in the label must be oriented towar...

Page 37: ...mended to use a 2A fuse in the power supply line Terminals Description Figure 16 Power supply and RS485 terminals 1 Power supply 8 30 VDC a 2A fuse is recommended 2 3 A RS485 port 4 B 6 2 Connection of the antennas GPRS 3G Z Wave optional and RF The terminals of the radio frequency and Z Wave antennas are SMA Sub Miniature version A You should verify which antenna corresponds to RF and which to GP...

Page 38: ...ht when the module is initialized and the top LED will blink in each GPRS session Figure 17 Location of the radio frequency and GPRS connector and the status LEDs The terminal of the GSM GPRS antenna is SMA Sub Miniature version A The GSM GPRS antenna should be installed following the ESD protections to prevent damage to the device 6 6 Digital outputs connection The models DL170 DL171 and DL172 ca...

Page 39: ...g diagram The device has 5 LEDs with the functions specified below Application Status LED App Status this LED should flash at a frequency of 1 Hz It will take approximately 60s to start blinking since the datalogger is switched on If the LED does not blink and it is either permanently off or permanently on it is a sign of a malfunction LOAD 1 LOAD 2 Terminal 12 Terminal 11 ...

Page 40: ...nce Description 1 Power 8 30 Vdc the use of a 2A fuse is recommended 2 3 A RS485 port 4 B 5 GND GND 6 TX RS232 port 7 RX 8 Vout aux Auxiliary digital output 5V 300mA 9 TX RS232 port console 10 RX 11 Out 1 Digital outputs 8 30 Vdc 100 mA max 12 Out 2 13 Out 3 14 Out 4 15 IN 1 Digital inputs 8 30 Vdc 16 IN 2 17 IN3 18 GND In GND input optional isolation of digital inputs ...

Page 41: ... port connection The same instructions as for the DL150 model should be followed see section 4 3 USB Wi Fi port connection p 24 7 4 Ethernet port connection The Ethernet port is in the opposite side to the terminals and close to the GPRS and RF antennas 7 5 GSM GPRS port connection The terminals of the radio frequency and Z Wave antennas are SMA Sub Miniature version A You should verify which ante...

Page 42: ...hernet port is in the opposite side to the terminals 8 4 GSM GPRS port connection The slot for the SIM card is located in the lower right part A SIM card is needed for the GSM GPRS communications There is a second slot for the µSD card The terminals of the radio frequency and Z Wave antennas are SMA Sub Miniature version A You should verify which antenna corresponds to RF and which to GPRS The GSM...

Page 43: ...72 Technical manual Version 1 01 Satel Spain 43 For easier installation we recommend not to use ferrules end sleeves to connect the cables to the electricity meters 4 5 and 6 in the model DL172 Figure 19 Electricity meters of the model DL172 Terminals diagram ...

Page 44: ......

Page 45: ...SETTING Manual Datalogger SenNet DL150 DL151 DL170 DL171 DL172 Versión 1 01 Satel Spain 45 DATALOGGER S SETTING ...

Page 46: ...the following At the home screen you can see the model of the datalogger the serial number which is the same serial number that is written on the sticker of the device the type of license code that depends on the number of electricity meters and the number of devices to be licensed and the software version Figure 20 Start screen to access to the datalogger s interface the screen may slightly vary ...

Page 47: ...tured Allows to visualise the data captured Input output Allows to read inputs or action the outputs RF Network Allows to see the devices connected to the Radio Frequency network of the datalogger Internal Meters Internal electricity meters this menu is not visible in the models without internal electricity meters DL150 and DL170 Configuration Allows to set up the equipment Datalogger Reboot Allow...

Page 48: ...captured overview On the left side of the screen you have the following options Refresh box When the box is selected the data are updated every minute Ask devices Allows to force a call to the devices Get CSV Allows to access to the folder structure and to the CSV files Channels Allows to access channels of different devices indicating the id of each channel The id is used both to calculate the MO...

Page 49: ...tivate and deactivate them by pressing the buttons o If the button is red the output is disabled o If the button is green the output is enabled Back back to the main menu Figure 23 Overview of the menu digital inputs Figure 24 Overview of the menu Outputs In this case the digital outputs DO1 DO2 and DO4 are enabled green and DO3 is disabled red The inputs and outputs of the datalogger can be contr...

Page 50: ...connections with the device Version the version of the internal software ROL it could be either router or end If it is router the device sends its own data to the datalogger and it also functions as a router that receives and forward signals from other devices If it is end the device only sends its own signals but it does not receive or routes signals from other devices Only the devices EMN RF Rep...

Page 51: ...atalogger is moved to different facilities Reset imeters To reset the counters after making any configuration changes current transformers Then the ABC steps should be followed A check the voltage phase sequence To test the phases It is done only once and allows you to check in three phase installations that connection to voltage phase sequence R S T has been respected Do not pass to step B until ...

Page 52: ...her the type of load that is metering INDUCTIVE CAPACITIVE RESISTIVE or NO LOAD To interpret the results of this step one must have electrical knowledge and must know the project in order to identify whether the result is as expected If it not the error will be that one for the CTs or Rogowski coils has been connected to a different phase and not to the correspondent one For instance it may be tha...

Page 53: ...171 DL172 Versión 1 01 Satel Spain 53 If the nominal value of the probe is less than 1000A and the resulting value of 5 per thousand is higher than 1A then 1A is used as the smallest threshold For Rogowski coils the minimal value taken into account is 5A ...

Page 54: ...e datalogger Events definition of events Router Actions DynDNS to configure a DynDNS account Platform parameters access to the configuration of the main energy and IoT platforms o Carriots set the specific parameters of the platform Carriots o SenNet API set the specific parameters of the platform SenNetAPI o Sofia2 credentials set the specific parameters of the platform SOfia2 Change password mod...

Page 55: ... DNS Parameters the connection to a server FTP FTP Parameters the radio frequency parameters RF Parameters and the storage Parameters Figure 29 Overview of the button General parameters within the menu Configuration The fields in the section can be different depending on the version of the app In order to save the changes made in this screen it is necessary to click on Accept and then click on the...

Page 56: ...ot necessary to send data to a server Only a few platforms require it NTP Server URL or IP address of the server used to synchronize the clock By default the internal clock uses time mit edu if nothing is specified The time is checked once a day If no synchronisation is needed then type NO If you want to set a GPRS connection the field Gateway IP must be filled with an asterisk delete all numbers ...

Page 57: ...perator of your SIM card If you do not want the datalogger to use the GPRS connection write an asterisk User the user set by the telephone operator Password the password set by the telephone operator PIN it is recommended to disable the PIN of the SIM card This field must be always filled in If the card does not have PIN then type for zeros 0000 Check ping IP or URL address to which the datalogger...

Page 58: ... PIN must always be filled in If the PIN of the SIM card is not enabled recommended introduce 0000 four zeros It is recommended to disable the PIN as it tends to give less connection problems Always introduce some value In the field check ping The option NO is not recommended since the datalogger will not check that the connection is working so it can lead to connection failures Figure 32 GPRS sta...

Page 59: ...resolve the DNS It is recommended to leave the default values DNS1 80 58 61 250 DNS2 80 58 61 256 If the connection is through Ethernet the DNS used as default will be If the connection is through GPRS the IP s will be the ones given by the telephone operator when establishing the GPRS session Figure 34 Detail view of the sections GPRS Parameters and DNS Parameters 15 1 6 FTP parameters FTP server...

Page 60: ... you need to send the data to the FTP server previously specified in the field FTP parameters Delete files older than days if you want the datalogger to automatically delete the files older than the number of days specified To configure the storage parameters it is essential to have a µSD card 15 2 Application parameters If you click on the button Application parameters you will be taken to a scre...

Page 61: ...s App id application identifier it is the id with which you want the data to be sent to the platform It is also used to store the data in CSV files if wanted Usually devices are assigned the numbers 1 2 3 n in the order in which they are appearing Click on the symbol for further details Communication params here you should indicate the port through which the device is connected to the datalogger T...

Page 62: ... consult the manufacturer s specifications of your device In Comm id you must put the Modbus ID of your device In App Id you should write the identification that you wish to give to your device Usually subsequent numbers are used 1 2 3 4 In communication params indicate how the meter is connected The options are RS232 or RS485 Name of device the name you want to give to your device Additional para...

Page 63: ...rding to the order of the devices in the table Communication params in this case this field must be left empty because the datalogger can communicate with the KNX network only through a KNX router that converts the KNX signals into RS232 This connection is internally configured in the application Name the name you wish to assign to the device Additional param addresses where the devices host the d...

Page 64: ... device in Configuration Application parameters in the table named List of devices Once this is done and the changes are saved the datalogger will start recording the data collected by the device Figure 39 The code needed to configure a Z Wave device Figure 40 How to introduce the code in the table List of Devices in the menu Configuration Application parameters After doing the any change on this ...

Page 65: ... possible to convert it into binary 42 decimal 101010 binary This means mean that there has been a sag event in phase 2 and a swell event in phases 1 and 3 15 4 Router This feature allows the datalogger to work also as a router for the signals sent by other devices It is only applicable if the datalogger is configured to send the data through GPRS It allows setting NAT rules that allow devices or ...

Page 66: ... 4IO Indicate the device s ID and separated by a comma the output on which to act For example o For SenNet 4IO RF 4529 1 where in this example 4529 is the serial number of the device and 1 is the output number 1 o For SenNet 4IO RS485 203 1 where 203 is the Modbus ID set and 1 is the output number 1 In the next line indicate the expression that defines the action following the instructions in the ...

Page 67: ...e IP of the last connection o To do this you must have a DynDNS account or create it at https account dyn com entrance Then register the account in the menu Configuration DynDNS You will see a screen like this Figure 42 Overview of the menu Configuration DynDNS After doing the any change on this screen click on Accept and then on the Save Changes button on the Configuration menu See 15 9 Save chan...

Page 68: ...alogger to Carriots is ApiKey in order to load data into Carriots administrator permissions are required You need also a password this appears in the section MY ACCOUNT in Carriots User Carriots user Apart from these data the datalogger must be uploaded into the platform with the MAC address entered without spaces or points and with capital letters The device with the MAC address with the datalogg...

Page 69: ...fterwards in Application Parameters Management platform you should choose SenNetAPI V1 or SenNetAPIV2 Finally you must save the data in the menu Configuration Save Changes To set the SenNet API you must use HTTP POST with JSON format Both the server and the URL used by the datalogger to send the data are configurable at the interface Request Method POST Headers User Agent sennet Content Type appli...

Page 70: ...captured channels with the channel s ID and the value Descriptions list of captured channels with the channel s ID and the description The list of available device types id descriptions and channels id descriptions can be downloaded from the datalogger s interface It can be found at Access Data Captured Channels Server Response If the reception is correct you should check the server response Ask 2...

Page 71: ... whether you want to send the data in encrypted form or not o Introduce 1883 for the unencrypted data submission o Introduce 8883 for the encrypted data submission Figure 44 Overview of the menu Configuration General parameters to configure Sofia 2 Then in Configuration Application parameters you sold introduce the following information Site name enter the name provided by Sofia2 Management platfo...

Page 72: ...e information at https viridityenergy com After doing the any change on this screen click on Accept and then on the Save Changes button on the Configuration menu See 15 9 Save changes p 72 15 8 Change password To change the password you will be asked to introduce your old password and the new password twice After doing the any change on this screen click on Accept and then on the Save Changes butt...

Page 73: ...n 0 based format you must subtract 40001 16 1 Datalogger s data Address Modicon format Description 40001 Datalogger s ID 40002 Software installation code 40003 Datalogger s software version 40004 SenNet Optimal s software version 40005 Seconds that remain until the next interrogation cycle 40006 Year for the date time setting 40007 Month for the date time setting 40008 Day for the date time settin...

Page 74: ...lure 4nn10 Not used 16 2 2 Device specific data In order to obtain a map of the device you should see the device s list of channels in the datalogger s interface click on Access Data Captured Channels and apply the following criteria Channel records with report id ID 4nnXX and 4nnYY where o nn is the ID meter o XX is 9 ID 2 o YY is XX 1 For example the registers of the channel whose ID 16 of the d...

Page 75: ...0 services version xml user ADMIN password MYPASSWORD Mandatory parameters user in this case the user is ADMIN In other dataloggers it can be different password In this case the password used is MYPASSWORD but each datalogger can have a different one Answer example 17 2 gprs xml Data about the GSM GPRS session Tags dl datalogger data Attributes o id MAC address o sn serial number GPRS data on the ...

Page 76: ...ve a different one Answer example data xml Latest data captured from the devices Tags dl datalogger s data Attributes o id mac address o sn serial number dev device Attributes o id device ID o name name of the device in the facility o type type of device o t timestamp of the capture ch information channel of the device s attributes o id channel ID o des channel description o u unit of measurement ...

Page 77: ...ng information channels 18 channels for SenNet Meter and 5 channels for MK Meter Each device is identified by a unique ID The device ID cannot be repeated within the same datalogger Each channel is identified by a specific device ID An example of response devices from the devices with ID 1 to 3 is shown below data_saved xml Captured data stored in the μSD card Tags dl datalogger s data Attributes ...

Page 78: ...tart date of the capture in format yyyy mm dd The maximum interval allowed is 365 days and the maximum file size downloadable is 500KB If the size is greater will skip all records from 500KB however the days transmitted will be complete If you want to know the list of channels it is recommended to make a request of a single day specifying the mode as mode first Example of a downloaded file SenNet ...

Page 79: ...1 DL170 DL171 DL172 Versión 1 01 Satel Spain 79 dev dl The maximum interval allowed is 365 days and the maximum file size downloadable is 500KB If the size is greater will skip all records from 500KB however the days transmitted will be complete ...

Page 80: ...alogger is constantly sending operating information through the RS232 console port Likewise it can perform some special maintenance functions such as Pressing the m key the device will ask for a password Enter sennet and you will access the options menu There it is possible to modify the basic settings such as changing the network settings By pressing the v key you will get information on the vers...

Page 81: ... should be used only by experts in Linux that know the internal structure of the datalogger files For special maintenance operations and if the datalogger access to internet is via external router it is important to enable the port 22 because it is the port used with SSH It is important to enable the port 22 used with SSH Access through SSH should be used only by experts in Linux that know the int...

Page 82: ...or further analysis in case of incidents in operation Parameters display and modification Software update Time setting The program LoggerControl uses TCP IP through the receiving port configured on the datalogger By default the port is the result of adding 100 to the datalogger id which is by default 5000 That is if no specific port has been configured the 5100 will be used There is an available v...

Page 83: ...PH with id 3 for Rogowski coils with 5000 A of rated current Figure 46 Example of configuration of three meters one three phase one single phase and another one three phase with Rogowski Path Configuration Application parameters 21 1 Real time monitoring The Internal Meters option has an option to make a plot in real time approx 5 lectures per second of the variables Power active reactive and appa...

Page 84: ...et DL150 DL151 DL170 DL171 DL172 84 Satel Spain Versión 1 01 Figure 47 Example of real time monitoring with Real Time Serial Data Plot The valid parameters for RS232 configuration are Speed 38400 Parity NONE Data bits 8 Stop bits 1 ...

Page 85: ...e screen you must log in with a special user name and password to customize the device By default the datalogger is supplied with the IP 192 168 1 35 If you have not changed it the way to access to the interface s home screen is by typing into your browser http 192 168 1 35 8080 If you are a Systems integrator ask Satel Spain for a special username and password to customize the datalogger Figure 4...

Page 86: ......

Page 87: ...For further information on SenNet products please contact sales satelspain com www sennetmonitoring com For technical support support satelspain com info satelspain com www sennetmonitoring com ...

Reviews: