Dataloggers SenNet DL150 / DL151 / DL170 / DL171 / DL172. Technical manual
Version 1.01
Satel Spain
37
6.
CONNECTION OF THE DL-170
6.1.
Connection to the power supply
The models DL170, DL171 and DL172 are powered with a battery or with a stabilized power source 8-
30 Vdc. For greater safety it is recommended the use of a 2A fuse in the power supply line.
The device can be powered with an external battery or with a stabilized power source. Your local
distributor of SenNet can provide you a suitable power supply
For greater safety it is recommended to use a 2A fuse in the power supply
line
Terminals
Description
Figure 16. Power supply and RS485
terminals
1
+
¡Power supply 8...30 VDC!
(a 2A-fuse is recommended)
2
-
3
A
RS485 port
4
B
6.2.
Connection of the antennas: GPRS/3G, Z-Wave (optional) and RF
The terminals of the radio frequency and Z-Wave antennas are SMA (Sub Miniature version A). You
should verify which antenna corresponds to RF and which to GPRS. All dataloggers DL170 have RF and
GPRS outputs.
The Z-Wave and RF antennas should be installed following the ESD
protections to prevent damage to the device
There are two LED lights that show the status of the RF module. If the radio is active, the bottom LED
will be on. The upper LED will blink whenever the datalogger makes a shipment by RF.