background image

SATEL 

KNX-BSA12L 

• KNX-BSA12H 

 connecting terminals for blind/shutter motors and power supply. 

 LEDs  indicating  state  of  blinds/shutters  /  channels  and  errors  (

  and 

 

–  green, 

 

– orange) – see Table 1. 

LED 

State of channel / blind/shutter 

 

 

 

 

 

 

no blind/shutter / channel not used 

 

 

 

blind/shutter not synchronized with module 

/

 

/

 

 

blind/shutter travel time detection (synchronization of 
blind/shutter with module) 

 

 

 

blind/shutter fully open 

 

 

 

position other than fully open 

 

 

 

blind/shutter move up 

 

 

 

blind/shutter move down 

 

 

 

restoring module factory settings 

 

Error type

 

 

 

 

blind/shutter error* when move up 

 

 

 

blind/shutter error* when move down 

 

– OFF,   – ON,   – flashing,  /  and  /  – LEDs are OFF and ON alternately. 

* incorrect position, mechanical jam, no power / supply circuit fault, motor overheating 
or obstacle detection by smart motor. 

Table 1. 

Blind/shutter  error  does  not  block  the  channel.  The  blind/shutter  travel  can  be 
controlled for the entire duration of the error. The error is automatically cleared when 
the  blind/shutter  reaches  the  end  position  in  the  opposite  direction  to  that  in  which  it 
was moving when the channel reported an error. 

Continuous operation for too long a time or repeated activation of the blind/shutter in 
very  short  intervals  can  cause  motor  overheating.  Re-starting  of  the  motor  is  only 
possible  after  it  has  cooled  down.  The  maximum  continuous  operation  time  of  the 
motor  and  the  time  required  for  cooling  down  after  overheating  are  specified  in  the 
motor manual. 

 buttons for manual control of blinds/shutters / channels 

– see Table 2. 

Button 

How to use 

Reaction 

 

short press 

blind/shutter move one step up* / stop 

long press 

blind/shutter fully open 

 

short press 

blind/shutter move one step down* / stop 

long press 

blind/shutter fully closed 

 + 

 

long press 

starts process of blind/shutter travel time 
detection (synchronization of blind/shutter with 
module) 

* function available in normal operating mode (not available in service mode). 
Pressing the button is interpreted by the module as a long press, when you press and 
hold down the button for longer than 1 second. 

Table 2. 

 

Summary of Contents for KNX-BSA12H

Page 1: ...KNX BSA12L 24 VDC KNX BSA12H 230 VAC Blind shutter Actuator Firmware version 1 02 knx bsa_en 09 20 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu...

Page 2: ...ized by the manufacturer shall void your rights under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and softw...

Page 3: ...guring global parameters 7 4 2 1 Weather alarms 8 4 3 Configuring channels 9 4 3 1 Blind shutter operating parameters 10 Motor 17 Shutter awning window 18 Venetian blind 18 4 3 2 Functions 20 Scene 1...

Page 4: ...s are configured in the ETS program in the same way for both modules except for defining operation of the vertical blinds as only the KNX BSA12L module supports this blinds 1 Features Communication wi...

Page 5: ...ror is automatically cleared when the blind shutter reaches the end position in the opposite direction to that in which it was moving when the channel reported an error Continuous operation for too lo...

Page 6: ...nsions based on the KNX BSA12L module The module takes up 4 units on the DIN rail 35 mm 2 2 Operating the module manually Manual operation allows you to control the movement of blinds shutters using t...

Page 7: ...12H reverse the wires controlling the direction of motor rotation Check the current consumption by the blind shutter motor if it is lower than the minimum current detected by the module the blind shut...

Page 8: ...eu ets must be imported into the program For detailed information on how to configure the module refer to section Configuring the module 3 1 Wiring diagram 4 Configuring the module Working parameters...

Page 9: ...ition control function will not be able to change the blind shutter position until the alarm is called off 4 2 Configuring global parameters The main working parameters of the module are defined in th...

Page 10: ...enetian blind vertical blind awning window Selecting the type of blind shutter will enable the communication objects to control its movement and display the Channel B tab The Vertical blind type of bl...

Page 11: ...me of the Frost alarm object 0 65535 seconds With the monitoring disabled field value 0 the alarm will only be triggered by receiving the Alarm telegram As good practice indicates monitoring time of t...

Page 12: ...lind shutter travel time may be detected by the module automatically recommended or can be determined based on a measurement taken The travel time is the time during which the blind shutter can be mov...

Page 13: ...o the upper end position It is advisable to automatically detect the time of movement by the module for all blinds shutters that make it possible Slat adjustment time This parameter applies to the sla...

Page 14: ...he slat position and adjustment time for a vertical blind only for the KNX BSA12L module Description of parameters Depending on the type of blind shutter selected for the channel A different parameter...

Page 15: ...select the manual detection fields that allow you to enter the measured values will be displayed in the tab see Shutter awning window and Venetian blind If you select manual detection for a blind shu...

Page 16: ...position at which the blind shutter can stop see Fig 10 0 100 default 10 If after stopping the distance between the blind shutter and the target position is greater the channel will report an error in...

Page 17: ...bstacle detection by smart motor Value 0 disables the cyclic telegram sending Interval of cyclic position sending frequency of sending a telegram with information about current blind shutter position...

Page 18: ...Move up down central communication object Changing the object value will trigger a channel response as a result of which the blind shutter will be moved up or down according to the value saved in the...

Page 19: ...the channel Disable Enable If you select Enable the Weather alarms tab will be displayed The parameter is available when the weather alarm functions are enabled in the module Weather alarms parameter...

Page 20: ...be taken Travel time up shutter travel time from the lower to the upper end position see Fig 4 6 and 7 0 480000 milliseconds The field is available if the yes option is selected for the Travel time in...

Page 21: ...option is selected for the Travel time in two directions parameter Travel time down time of travel of Venetian blind from the upper to the lower end position see Fig 4 0 480000 milliseconds The field...

Page 22: ...to control the position of blinds by defining the correct percentage values of opening for the first and second scenes from the pair percentage value of opening before calling scenes channel A 0 chann...

Page 23: ...with value 0 from the Call scene 1 bit 1 2 communication object 0 100 0 upper end shutter position 100 lower end shutter position see Fig 4 6 and 7 Scene 2 delay time that must elapse from receiving t...

Page 24: ...ind position 100 lower end blind position see Fig 4 and 5 Scene 1 position of slats position to which the slats will be set in response to the telegram with value 0 from the Call scene 1 bit 1 2 commu...

Page 25: ...from the bus If the object value has not been changed by the learning function the default value will be set Initial values for the other scenes are defined in the same way as for the 1 2 pair Scene...

Page 26: ...g scenes from bus parameter default value defined in the program If the object receives a telegram with the scene number Scene 1 8 number field the shutter is set to position corresponding to the valu...

Page 27: ...larm i e their hierarchy where 1 highest priority 3 lowest priority 1 Frost 2 Rain 3 Wind 1 Frost 2 Wind 3 Rain 1 Rain 2 Frost 3 Wind 1 Rain 2 Wind 3 Frost 1 Wind 2 Frost 3 Rain 1 Wind 2 Rain 3 Frost...

Page 28: ...he object assumes the value 1 the blind shutter will be set to the position defined and the channel will be locked Unlocking of the channel is only possible when the object assumes the value 0 When un...

Page 29: ...ountdown will be started again reset The blind shutter position set by using this object can only be changed as a result of a higher priority alarm see Weather alarms or by the position forcing functi...

Page 30: ...absolute position slats percentage 1 byte DPT 5 001 C W The object will be enabled if you select Enable for the Central absolute position parameter in the tab for configuring the settings of the chann...

Page 31: ...in the Interval of cyclic device error alarm sending field in the Global tab Telegram 1 error in one of the channels 0 module is working correctly Flag C communication R read W write T transmit U upda...

Page 32: ...a 1 bit object 0 step up by the value defined in the Step value field 1 step down by the value defined in the Step value field when the blind shutter or slats are moving 0 STOP 1 STOP 19 Channel A De...

Page 33: ...shutter in the Channel A field Global tab It enables sending a telegram with information about the current position of the blind shutter The telegram is always sent after the travel is completed The p...

Page 34: ...etian blind Telegram 1 error in the channel 0 channel is workin correctlly Flag C communication R read W write T transmit U update Functions Channel communication objects No Object name Object functio...

Page 35: ...ject with number X Y enables the current blind shutter position percentage value of opening to be assigned to the 1 bit scene with number X and Y Telegram 0 current blind shutter position will be assi...

Page 36: ...L 24 VDC KNX BSA 12H 230 VAC In rated current KNX BSA 12L 6 A KNX BSA 12H 6 A Connections Maximum wire cross section 2 5 mm2 Maximum tightening torque 0 5 Nm KNX parameters Maximum time of reaction to...

Reviews: