SATEL
KNX-BSA12L
• KNX-BSA12H
27
Global communication objects
No.
Object name
Object function
Data type
Flags
1
General
Device
operation status
1 bit,
DPT 1.001
C, R, T
The object sends a telegram cyclically to the KNX bus with information about the module
status. To disable the sending, you can enter the value “0” into the “Interval of cyclic device
status sending” field, in the “Global” tab.
Telegram: 1 = the module is running.
2
Safety
Wind alarm
1 bit,
DPT 1.005
C, W
The object will be enabled
if you select “Enable” for the “Weather alarms” parameter in the
“Global” tab. It can receive from the KNX bus 1-bit telegrams sent cyclically by the wind
sensor or weather station. If, within the defined monitoring time, the object receives no
resetting telegram or receives the activating telegram, an alarm will be triggered and the
blind/shutter will set to the position defined as response to the
“Wind” alarm (see “Weather
”). The channel is locked and does not process any incoming telegrams.
The channel can only be unlocked when the object has received the unlocking telegram
(see
“Weather alarms”). If, during the monitoring time, a telegram with the value opposite to
that triggering the alarm is received, the countdown will be started again (reset).
The blind/shutter position set by using this object can only be changed as a result of
a
higher priority alarm (see “Weather alarms”) or by the position forcing function.
3
Safety
Rain alarm
1 bit,
DPT 1.005
C, W
The object will be enabled if you select “Enable” for the “Weather alarms” parameters in the
“Global” tab. The object can receive from the KNX bus 1-bit telegrams sent cyclically by the
rain sensor or weather station. For other information, see the “Wind alarm” object.
4
Safety
Frost alarm
1 bit,
DPT 1.005
C, W
The object will be enabled if you select “Enable” for the “Weather alarms” parameters in the
“Global” tab. The object can receive from the KNX bus 1-bit telegrams sent cyclically by the
rain
sensor or weather station. For further information, see the “Wind alarm” object.
5
Central
Move up/down
1 bit,
DPT 1.008
C, W
The object will be enabled if you select “Enable” for the “Central move up/down” parameter
in the tab for configuring the channel settings
(e.g. “A: Shutter”). It allows you to start the
travel of both blinds/shutters connected to the module by using one telegram.
The blind/shutter travel started by
the object can be stopped by the “STOP” telegram or
when the blinds/shutters reach the end position. Only the
channels for which “Enable” is
selected for the “Central move up/down” parameter will respond to a change of the object
value.
Telegram:
0 = up, 1 = down