
37
5.21 Data Log Registers
Data log records are read via a data log window, one for each data log partition. Reading from this window
always returns the next record logged in the partition. All registers within one window must be read at once using
a single request. After reading each record, the partition queue pointer is shifted forward until the last logged
record has been read. After that, the exception code 98 is returned in the record's first register. It should be
checked before accepting the record. To restore the queue to the origin, a zero must be written to the partition
queue reset register (see Section 5.5).
Table 5-49 Data Logs Window Registers
Data log window
Registers (see Table 5-50)
Data log #1 window
1120-1161
Data log #2 window
1162-1203
Data log #3 window
1204-1245
Data log #4 window
1246-1287
Data log #5 window
1288-1329
Data log #6 window
1330-1371
Data log #7 window
1372-1413
Data log #8 window
1414-1455
Table 5-50 Data Log Window Registers
Parameter
Offset
Size,
byte
Direction
Range
Trigger setpoint number
+0
2
R
1-16,
97 = record corrupted
98 = no more records
99 = no records logged
Hundredths of second
+1
2
R
0-99
2
2
R
0-59
Minute
+3
2
R
0-59
Hour
+4
2
R
0-23
Day
+5
2
R
1-31
Month
+6
2
R
1-12
Year +7
2
R
0-99
Re8
2
R
0
The number of parameters
in the record
+10 2 R
1-16
Log parameter #1 value
+11
+12
4
R
see Table 5-18
Log parameter #2 value
+13
+14
4
R
see Table 5-18
...
Log parameter #16 value
+40
+41
4
R
see Table 5-18
The log parameter value is read as 16-bit ordinal register or 32-bit counter. For the value range and
conversion scales, refer to Table 5-18.
When reading the data log window registers, those that reside outside of the specified partition record size will be
read as zeros. The actual number of parameters in the record is indicated in the log window register at offset
+10.
5.22 Min/Max Log Registers
These registers allow you to read time-stamped Min/Max logs in 16-bit Modbus registers using LIN3 conversion.
From 1 to 12 adjacent records can be read at a time via the Min/Max log windows. The starting window #1 can
be mapped to any Min/Max log parameter listed in Table 5-18 by writing the parameter ID to the Min/Max log
mapping register. This register must be written before reading the Min/Max log windows. Note that through
Min/Max log windows, you can read only adjacent parameters within the same Min/Max log data group. Reading
parameters outside of the selected Min/Max log data group will return zero.