Table 5-32 Pulsing Setup Registers
Parameter
Offset
Size,
byte
Direction
Range
Output parameter ID
+0
2
R/W
see Table 5-33
Number of unit-hours per pulse
+1
2
R/W
1-9999
Table 5-33 Pulsing Output Parameters
Pulsing parameter
ID
None
0
kWh import
1
kWh export
2
kvarh import
4
kvarh export
5
kvarh total (absolute)
6
kVAh total
7
5.16 Relay Operation Control Registers
These registers allow the user to manually override setpoint relay operations. Either relay may be
manually operated or released using commands sent via communications.
NOTES
1. A relay allocated as a pulsing relay may not be manually operated or released. When a relay is
allocated for pulsing, it automatically reverts to normal operation.
2. A relay is energized when manually operated, and is de-energized when manually released.
Table 5-34 Relay Operation Control Registers
Parameter
Register
Size,
byte
Direction
Range
Relay #1 control status
3244
2
R/W
see Table 5-35
Relay #2 control status
3245
2
R/W
see Table 5-35
Table 5-35 Relay Operation Status
Operation status
Value
Normal operation
0
Force operate
1
Force release
2
5.17 Pulse Counters Setup Registers
Table 5-36 Pulse Counters Registers
Counter
Setup registers (see Table 5-37)
Counter #1
2940-2941
Counter #2
2942-2943
Counter #3
2944-2945
Counter #4
2946-2947
Table 5-37 Pulse Counter Setup Registers
Parameter
Offset
Size,
byte
Direction
Range
Associated digital input ID
+0
2
R/W
see Table 5-38
Scale factor (number of units
per input pulse)
+1 2 R/W 1-9999