16
5.4 Communications Setup Registers
Table 5-4 Communications Setup Registers
Parameter
Register
Size,
byte
Direc-
tion
Range
Reserved 2344
2
R
Read as 65535
Interface
2345
2
R/W
0 = RS-232
1 = RS-422
2 = RS-485
Address
2346
2
R/W
1 to 247
Baud rate
2347
2
R/W
0 = 110 bps
1 = 300 bps
2 = 600 bps
3 = 1200 bps
4 = 2400 bps
5 = 4800 bps
6 = 9600 bps
7 = 19200 bps
Data format
2348
2
R/W
1 = 8 bits/no parity
2 = 8 bits/even parity
Incoming flow control
(handshaking)
2349
2
R/W
0 = no handshaking
1 = software handshaking
(XON/XOFF protocol)
2 = hardware handshaking
(CTS protocol)
Outgoing flow control
(RTS/DTR)
2350
2
R/W
0 = RTS signal not used
1 = RTS permanently
asserted (DTR mode)
2 = RTS asserted during the
transmission
When changing the instrument address, baud rate or data format, the new communications parameters will take
effect 100 ms after the instrument responds to the master's request.
5.5 Reset/Clear Registers
Table 5-5 Reset/Clear Registers
Function
Register Size,
byte
Direc-
tion
Reset
value
Clear total energy registers (E)
3404
2
W
0
Clear total maximum demand
registers
3405
2
W
0 = all maximum demands
1 = power demands (E)
2 = volt/ampere demands
Clear TOU energy registers (E)
3406
2
W
0
Clear TOU maximum demand
registers (E)
3407 2
W 0
Clear pulse counters
3408
2
W
0 = all counters
1-4 = counter #1 - #4
Clear Min/Max log
3409
2
W
0
Clear event log (E)
3410
2
W
0
Clear data log
3411
2
W
0-7 = log #1 - #8
16 = all data logs
Reserved 3412
2
Reserved 3413
2
Reserved 3414
2
Restore event log queue pointer
(E)
3415 2
W 0
Restore data log queue pointer (E) 3416
2
W
0-7 = log #1 - #8
(E) available in the PM171E