14
Parameter
Register Size,
Direc-
Unit
Scale
Con-
byte
tion
Low
High
version
Current TDD L1
306
2
R
0.1%
0
100.0
LIN3
Current TDD L2
307
2
R
0.1%
0
100.0
LIN3
Current TDD L3
308
2
R
0.1%
0
100.0
LIN3
The parameter limits are as follows:
Imax
(20% over-range) = 1.2
×
CT primary current [A]
Direct wiring (PT Ratio = 1):
Vmax
(690 V input option) = 828.0 V
Vmax
(120 V input option) = 144.0 V
Wiring via PTs (PT Ratio > 1):
Vmax
(690 V input option) = 144
×
PT Ratio [V]
Vmax
(120 V input option) = 144
×
PT Ratio [V]
Pmax
= (Imax
×
Vmax
×
3)/1000 [kW ] if wiring mode is 4LN3 or 3LN3
Pmax
= (Imax
×
Vmax
×
2)/1000 [kW ] if wiring mode is 4LL3, 3OP2, 3DIR2, 3OP3 or 3LL3
Positive readings of kvarh net
Negative readings of kvarh net
To get block interval demand readings, specify the number of demand periods equal to 1 (see Table 5-2).
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring
mode, they will be line-to-line voltages.
(E) available in the PM171E
NOTE
Writing a zero to one of registers 280-286 causes reset of all maximum demands. Writing a zero to one
of registers 287-294 and 301-302 causes reset of all accumulated energies. This does not apply to the
TOU system registers.
5.2 Basic Setup Registers
Table 5-2 Basic Setup Registers
Parameter
Register Size,
byte
Direc-
tion
Range
Wiring mode
2304
2
R/W
0 = 3OP2, 1 = 4LN3,
2 = 3DIR2, 3 = 4LL3, 4 = 3OP3,
5 = 3LN3, 6 = 3LL3
PT ratio
2305
2
R/W
10 to 65000
×
0.1
CT primary current
2306
2
R/W
1 to 50000 A
Power demand period (E)
2307
2
R/W
1,2,5,10,15,20,30,60 min,
255 = external synchronization
Volt/ampere demand period
2308
2
R/W
0 to 1800 sec
Averaging buffer size
2309
2
R/W
8, 16, 32
Reset enable/disable
2310
2
R/W
0 = disable, 1 = enable
Reserved
2311
2
R
Read as 65535
The number of demand periods (E)
2312
2
R/W
1 to 15
Reserved
2313
2
R
Read as 65535
Reserved
2314
2
R
Read as 65535
Nominal frequency
2315
2
R/W
50, 60, 25
(Hz)
Maximum demand load current
2316
2
R/W
0 to 50,000 A
(0 = CT primary current)
The wiring mode options are as follows:
3OP2 - 3-wire open delta using 2 CTs (2 element)
4LN3 - 4-wire WYE using 3 PTs (3 element), line to neutral voltage readings
3DIR2 - 3-wire direct connection using 2 CTs (2 element)
4LL3 - 4-wire WYE using 3 PTs (3 element), line to line voltage readings
3OP3 - 3-wire open delta using 3 CTs (2 1/2 element)
3LN3 - 4-wire WYE using 2 PTs (2 1/2 element), line to neutral voltage readings
3LL3 - 4-wire WYE using 2 PTs (2 1/2 element), line to line voltage readings
25 Hz - special order
(E) available in the PM171E