Chapter 5 Setting Up the ETC II
Configuring Data Server
44
ETC II Network Communicator
The following table lists available options.
Parameter
Options
Default
Description
XPW Server IP Address
207.232.60.18 The IP address of the
eXpertPower server
XPW Server Port
0-65535
5001
The TCP service port of the
eXpertPower server
XPW Client Enabled
NO, YES
NO
Enables operations of the
eXpertPower client
Time to Next Session, min 1-99999
The time remaining to the
next connection session
Configuring Data Server
Using HyperTerminal or Telnet
See
Data Server
in Chapter 3 for information on Data server operations.
To view or change the Data server settings, type
datasrv
and press Enter.
>datasrv
You will be prompted for the password. The factory-set password is 0 unless
you have changed it in your ETC II.
Enter password:*
Data Server Configuration Commands
------------------------------------
h - Display this text
p - Server parameters
s [N] - Set address range *
i [N] - Display address range settings *
q - Quit menu
*(N - address range number)
Data server>
Data Server Options
To view the Data server options, type
i
and press Enter.
Data server>i
Data Server Configuration
---------------
---------------------
Data server disabled
Continuous polling disabled
Polling interval 1 min
Logging interval 1 (x1min)
To setup or change the Data server options, type
p
and press Enter. To
change an option, type your new setting after the prompt and press Enter. To
leave the setting unchanged, just press Enter. Refer to the table below for
the available options and their explanation.
Data server>p
Data server: disabled
New [y/n]:
Continuous polling: disabled
New [y/n]:
Polling interval: 1 min
New: