I - 81
SM830052
1
ECO MULTI SYSTEM Unit Specifications
7. Concealed Duct Type
MODEL No.
Indoor Unit
SPW-U253GH56
POWER SOURCE
220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
7.3
8.0
BTU / h
25,000
27,000
Air circulation (Hi / Me / Lo)
m
3
/ h
1,260 / 1,080 / 780
External static pressure (High)
mmAq (Pa)
5 (49): at shipment, 10 (98): using the booster cable
Moisture removal (High)
Liters / h
3.2
—
ELECTRICAL RATINGS
Voltage rating
V
220 - 230 - 240
Available voltage range
V
198 – 264
Running amperes
A
0.84 -
0.89 -
0.90
0.84 -
0.89 - 0.90
Power input
W
180 -
200 -
210
180 -
200 -
210
Power factor
%
97 -
98 -
97
97 -
98 -
97
Fan motor locked rotor amperes
A
1 - 1 - 1
FEATURES
Controls / Temperature control
Microprocessor / I.C. thermostat
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
3 and Automatic control
Air filter
Field supply
Refrigerant control
Electronic refrigerant control valve
Operation sound
(Hi / Me / Lo)
dB-A
36 / 31 / 26
using the booster cable (Hi / Me / Lo)
dB-A
41 / 38 / 35
Refrigerant tubing connections
Flare type
Refrigerant tube
Narrow tube mm (in)
9.52 (3 / 8)
*
diameter
Wide tube
mm (in)
15.88 (5 / 8)
Drain connection
25 A, OD32 mm
Drain pump
Max. head 25 cm above drain connection
Remote Controller
Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories
Optional / Booster cable
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Dimensions
Height
mm (in)
310 ( 12 - 1 / 4)
380 ( 15
-
)
Width
mm (in)
1,050 ( 41 - 3 / 8)
1,249 ( 49 - 1 / 4)
Depth
mm (in)
665 ( 26 - 1 / 4)
866 ( 34 - 1 / 16)
Net weight
kg (lb)
41 (
90
)
Shipping weight
kg (lb)
50 (
110
)
Shipping volume
m
3
(cu. ft)
0.411 ( 14.5
)
Unit specifications (D)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Heating: Indoor air temperature 20
°
C DB
, Outdoor air temperature 7
°
C DB / 6
°
C WB
*
Use the “Tube connector” (accessory part with unit).