ECO MULTI SYSTEM Unit Spesifications
SM830052
I - 20
1
2. 4-Way Air Discharge Semi-concealed Type
Unit specifications (B)
MODEL No.
Indoor Unit
SPW-X183GH56
POWER SOURCE
220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
5.6
6.3
BTU / h
19,000
21,000
Air circulation (Hi / Me / Lo)
m
3
/h
900 / 780 / 660
Moisture removal (High)
Liters/h
3.0
—
ELECTRICAL RATINGS
Voltage rating
V
220 - 230 - 240
Available voltage range
V
198 – 264
Running amperes
A
0.60 -
0.62 -
0.63
0.37 -
0.40 - 0.42
Power input
W
130 -
140 -
150
80 -
90 -
100
Power factor
%
98 -
98 -
99
98 -
98 -
99
Fan motor locked rotor amperes
A
1 - 1 - 1
FEATURES
Controls / Temperature control
Microprocessor / I.C. thermostat
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
3 and Automatic control
Air filter
Washable, easy access
Refrigerant control
Electronic refrigerant control valve
Operation sound (Hi / Me / Lo)
dB-A
37 / 35 / 30
Refrigerant tubing connections
Flare type
Refrigerant tube diameter
Narrow tube mm (in.)
9.52 (3 / 8)
Wide tube
mm (in.)
15.88 (5 / 8)
Drain connection
25 A, OD32 mm
Drain pump
Max. head 25 cm above drain connection
Remote Controller
Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories
Optional / —
DIMENSIONS & WEIGHT (include ceiling panel)
Unit dimensions
Package dimensions
Dimensions
Height
mm (in.)
328 ( 12 - 29 / 32)
410 ( 16 - 3 / 8)
Width
mm (in.)
860 ( 33 - 7 / 8)
988 ( 38 - 7 / 8)
Depth
mm (in.)
860 ( 33 - 7 / 8)
988 ( 38 - 7 / 8)
Net weight
kg (lbs.)
29 (
64
)
Shipping weight
kg (lbs.)
46 (
101
)
Shipping volume
m
3
(cu. ft)
0.400 ( 14.1
)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Heating: Indoor air temperature 20
°
C DB
, Outdoor air temperature 7
°
C DB / 6
°
C WB