II - 7
Processes and Functions
SM830052
2
7. Room Temperature Control
The thermostat is switched on/off by
∆
T as follows.
∆
T = (Room temperature) – (Set temperature)
Remote control thermostat
Room temperature = remote control sensor
Body thermostat
Room temperature = (Body sensor) – (Shift temperature*)
* Shift temperature (valid only for heating)
0 ˚C ~ 10 ˚C can be selected with the remote controller simple setting mode.
(Factory settings: floor standing type ----- 0 deg; wall-mounted type ----- 2 deg; other types ----- 4 deg)
Supplement:
(1)
After thermo.-on, it will not thermo.-off for 3 minutes due to
∆
T .
However, for heating, if the indoor coil E2 temperature
]
64 ˚C, it will thermo.-off within 5 minutes (over load
protection).
(2)
After thermo.-off, it will not thermo.-on for 1 minute.
For cooling or dehumidifying, it will not thermo.-on if the indoor coil E1 or E2 temperature < 6 ˚C.
(3)
At the start of operation, the slope is down (thermo.-on).
(4)
When the system is set for test operation, it will not thermo.-off for 60 minutes (forced thermo.-on).
+1.0
0
-1.0
Cooling
Heating
: THERMO. OFF
: THERMO. ON
+1.0
0
-1.0
0319_M_I
T
T