II - 11
Processes and Functions
SM830052
2
12. Auto-flap Control
12-1. X, S, T Type
The auto-flap controls the air flow to one of the five vertical levels.
X type (4-way)
S type (2-way)
T type
Operation mode
Flap position
Automatic setting
Manual setting
Cooling / drying
F2
F1 · F2 · F3 · swing
Fan
F2
F1 · F2 · F3 · F4 · F5 · swing
Heating
F4
F1 · F2 · F3 · F4 · F5 · swing
Heating preparation
F2 (Original position after release)
(1)
When the unit is stopped, the auto-flap returns to the F5 position.
(2)
When the airflow direction is set manually (optional setting), the auto and swing settings will be released. To return
to automatic airflow direction, change the operation mode.
(3)
Once auto-flap is set, it is input into the microcomputer memory.
(4)
When the operation mode is changed, the unit begins a sensing operation. (If a search for sensing points does not
succeed in one minute, only the flap moves.)
Remote controller
Wired remote
Wireless remote controller
System controller
configuration
controller (RCS-SH80TG)
(RCS-SH80TGWL)
(SHA-KC64TG)
System
Single
Group control
Single
Group control
Auto-flap
Swing
‡
‡
‡
‡
%
(*1)
Air direction setting
‡
‡
‡
‡
%
(*1)
*1:
Only possible when remote control unit is not used.
For group control, the settings are for the complete group.
12-2. K Type
When the “SWEEP” button is pressed, swing starts and when it is pressed again, the flap stops in place.
20
°
Auto-flap
20
°
30
°
40
°
40
°
F1
F2
F2
F2
F3
F3
F3
F4
F4
F4
F5
F1
F1
F5
F5
0329_M_I
Heating
Cooling