ECO MULTI SYSTEM Unit Spesifications
SM830052
I - 4
1
1. Outdoor Unit
MODEL No.
Outdoor Unit
SPW – C483GY8
POWER SOURCE
380 - 400 - 415 V / 3 phase / 50Hz
PERFORMANCE
Cooling
Capacity
kW
14
BTU / h
47,800
Air circulation (Hi)
m
3
/min(cu. ft/min)
84 (2,970)
ELECTRICAL RATINGS
Voltage rating
V
380 - 400 - 415
Available voltage range
V
342 - 456
Running amperes
A
8.5 -
8.5 -
8.8
Max. running amperes*
A
10.0 -
9.9 -
10.0
Power
input
kW
4.87 - 4.92 -
4.97
Max. power input*
kW
5.90 - 5.91 -
5.96
Power factor
%
87 -
84 -
79
C.O.P
W/W
2.87 - 2.85
-
2.82
Compressor locked rotor amperes
A
62 -
65 -
67
FEATURES
Controls
Microprocessor
Defrost control
Reverse cycle, microprocessor control
Service function
Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment
kg
R22 - 3.0
Refrigerant control
Electronic Refrigerant Control Valve
Operation sound (Hi)
dB-A
55
REFRIGERANT TUBING
Limit of tubing length
m(ft.)
50 (164)
Limit of elevation difference
m(ft.)
Outdoor unit is higher than indoor unit : 40 (131)
between the two units
Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube
Narrow tube mm (in)
9.52 ( 3 / 8 )
outer diameter
Wide tube
mm (in)
19.05 ( 3 / 4 )
Refrigerant tubing kit / joint kit
Optional
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
mm(in)
1,235 (48 - 20 / 32)
1,326 (52 - 7 / 32)
Width
mm(in)
940 (37
)
1,016 (40
)
Depth
mm(in)
340 (13 - 12 / 32)
416 (16 - 12 / 32)
Net weight
kg(lb)
107 (
236
)
Shipping weight
kg(lb)
114 (
251
)
Shipping volume
m
3
(Cu. ft.)
0.56 (
19.8 )
Unit specifications (B)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19.0
°
C WB
, Outdoor air temperature 35
°
C DB
* Full load conditions at Indoor / outdoor capacity ratio 100 %
Cooling: Indoor air temperature 32
°
C DB / 22.5
°
C WB , Outdoor air temperature 43
°
C DB / 25.5
°
C WB