![Sanyo ECO G SPW-GU055XH Technical Data & Service Manual Download Page 174](http://html.mh-extra.com/html/sanyo/eco-g-spw-gu055xh/eco-g-spw-gu055xh_technical-data-and-service-manual_359219174.webp)
4-28
W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
2. Indoor Unit
Unit Specifications
MODEL NAME
Heat Recovery with Direct-expansion Coil
MODEL No.
SPW-GU105XH
POWER SOURCE
220 - 230 - 240 V / single-phase / 50 Hz
PERFORMANCE
Cooling
Heating
Capacity
Total
kW
9.12
10.69
Expansion Coil
kW
5.6
6.3
Total heat
exchanger
Enthalpy exchange
efficiency
Summer(%)
58
Winter(%)
66
Temperature exchange
%
73
Air circulation (High at 230 V)
M
3
/ h
1,000
Moisture removal (High)
Liters / h
3.0
–
External Static
Pressure
Air Charge
Pa
135
Air Discharge
Pa
176
ELECTRICAL RATINGS
Voltage rating
V
220
230
240
220
230
240
Available voltage range
V
198 - 264
198 - 264
Running amperes
A
3.7
3.5
3.4
3.7
3.5
3.4
Power input
kW
0.798
0.798
0.798
0.798
0.798
0.798
Power factor
%
99
99
99
99
99
99
Starting amperes
A
9.2
FEATURES
Heat exchanger
Direct-Expansion Coil: Plate finned tube
Total heat exchanger: Static conversion
Controls
Microprocessor
Fan speeds
High, (Low*)
Air filter
Air Charge
Long-life filter (Washable)
Air Discharge
Long-life filter (Washable)
Refrigerant control
Electronic Expansion Valve
Operation sound
dB - A
52
Refrigerant tubing connections
Flare type
Refrigerant tube
diameter
Liquid tube
mm (in.)
6.35 (1/4)
Gas tube
mm (in.)
12.7 (1/2)
Drain connection
25A (Connection port R1 screw)
Drain pump
–
Duct connection port
mm
ø 300 × 4
Timer Remote Controller
Optional (RCS-TM80BG)
High performance filter
Optional (65% colorimetric)
Humidifier
Optional (natural evaporating type)
Supplied accessories
External static pressure line switching connector,
Insulation, Clamper, Installation and Operating Manual.
DIMENSIONS & WEIGHT
Unit dimensions
Height
mm
450
Width
mm
1,903
Depth
mm
1,220
Net weight
kg
200
Rated conditions
• (Low*): When the supplied external static pressure line switching connector is connected.
• The numerical value within the parenthesis of fresh air conditioning load throughput is value of the heat recovery amount due to total heat
exchange.
• As for the Direct-Expansion Coil efficiency, when it is run under the test conditions stated below
Cooling: Direct-Expansion Coil port temperature 27 °C DB and 19 °C WB (discharge air), Outdoor air inlet temperature 35 °C DB and 24 °C
WB (charge air).
Heating: Direct-Expansion Coil port temperature 20 °C DB (discharge air), Outdoor air inlet temperature 7 °C DB and 6 °C WB (charge air)
• Efficiency of the total heat exchanger depends on the following conditions.
Summer: Indoor temperature 27 °C DB & 20 °C WB (discharge air), Outdoor temperature 35 °C & DB 29 °C WB (charge air).
Winter: Indoor temperature 20 °C DB & 14 °C WB (discharge air), Outdoor temperature 5 °C & DB 2 °C WB (charge air).
• The operation sound is measured when the unit is connected to the duct and operated in the anechoic room, associated with the value
measurement directly 1.5m from under the unit.
Once true installation effects taken into account, the actual levels will exceed the indicated values due to reflections off adjacent surfaces and
peripheral noise.
• The changes of H/L of external static pressure depend on the plug equipped connector. However, it will not affect the remote control indication
and will display the HIGH mark.
• This unit has no solvent resistance. Please pay attention to the installation site.
Summary of Contents for ECO G SPW-GU055XH
Page 2: ...i ...
Page 3: ...ii ...
Page 146: ......
Page 198: ......
Page 200: ...6 2 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit 1 Electric Wiring Diagram SPW C0705DXHN8 ...
Page 201: ...6 3 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C0705DXHN8 ...
Page 203: ...6 5 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C0905 C1155DXHN8 ...
Page 205: ...6 7 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C1305 C1405DXHN8 ...
Page 207: ...6 9 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 2 Schematic Diagram SPW GU055 075 105XH ...
Page 208: ......
Page 242: ......