3-20
Control of W-2WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
Fig. 3-22
1
3
2
4
6
5
Face plate
Remove
Screws
M4 × 25 (2)
Receiver unit
Spacer
2
(provided 200mm
power cable)
Plate
mounting
Screws
M4 × 25
Screws
M4 × 40
Wood
screws
1
2
3
4
5
No.
Parts
Q'ty
No.
6
7
8
9
1
1
2
Parts
Q'ty
4
2
1
1
Separate
receiver unit
Spacer
Wire joints
Clamp
Pattern template
95 × 51
2
unit: mm
2. Wireless Remote Controller
RCS-BH80AG.WL for AD, U, D, F, FM Type
2-18. Accessories Supplied with Separate Receiver Unit
2-19. Important Information for Installation of 1
Separate Receiver Unit
<Installation location>
Do not install in a location where the air contains oil mist,
such as in a kitchen or factory.
Do not install next to a window, or in any other location
directly exposed to sunlight and outside air.
Do not install nearby devices which can be expected to
produce electrical noise, such as elevators, automatic
doors, and industrial sewing machines.
If the receiver unit is installed near a rapid-start type or
inverter-type fluorescent lamp (a lamp which does not
include a glow lamp), it may not be possible to receive the
wireless remote controller signal in some cases. In order
to prevent interference from fluorescent lamps, leave a
minimum of 2 meters between the receiver unit and the
fluorescent lamps, and install the receiver unit in a location
where it can receive the wireless remote controller signal
when the fluorescent lamps are lit.
2-20. How to Install the Separate Receiver Unit
To avoid malfunction of the remote controller, do not
assemble or run remote control wiring together with the
power cables, and do not enclose them in the same metal
conduit.
When the power unit induces electrical noise, it is
recommended that a noise filter or the like be installed.
NOTE
Summary of Contents for ECO G SPW-GU055XH
Page 2: ...i ...
Page 3: ...ii ...
Page 146: ......
Page 198: ......
Page 200: ...6 2 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit 1 Electric Wiring Diagram SPW C0705DXHN8 ...
Page 201: ...6 3 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C0705DXHN8 ...
Page 203: ...6 5 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C0905 C1155DXHN8 ...
Page 205: ...6 7 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C1305 C1405DXHN8 ...
Page 207: ...6 9 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 2 Schematic Diagram SPW GU055 075 105XH ...
Page 208: ......
Page 242: ......