Creating Timer Groups
The schedule timer can be set for 6 time status changes.
These can be used to create up to 8 groups (timer groups).
For systems in which schedule timers are used, set the timer
groups to match the central control addresses of the indoor
units that will be subject to group timer control.
The timer-group settings for the schedule timer involve as-
signment of central control addresses. Therefore, use the
system controller (or other central control device) or wired
remote controllers to set the central control addresses of the
indoor units, then make the schedule timer settings.
Procedure for making fixed timer group settings (fixed groups)
(1) First, use a different central control device (system controller or other device) or the wired remote controllers to set the cen-
tral control addresses, as assigned in the figure above, to the indoor units that will be subject tom group timer control.
(2) Next, use S41 switches 2 and 3 to set the number of timer groups you wish to create.
(3) Finally, turn ON the schedule timer power. Initial communications are performed. (SCAn blinks in the display.) The normal
display appears after several minutes, and the timer group settings are confirmed.
Procedure for making manual timer group settings (manual group assignments)
Manual timer group settings allow central control addresses to be assigned freely within the timer groups.
(1) Turn ON S41 setting switches 2 and 3, then turn ON the power. Restart and initial communications are performed. (SCAn
blinks in the display.) The normal display appears after several minutes.
(2) When the normal display appears, press and hold the schedule timer
button, the timer
button, and the
button for 4 seconds or longer. “Ad-01” appears, blinking, in the current time display. (Ad indicates “address” and 01 is the
central address number.)
(3) Use the
button in the area to select the timer group. Then use the
button in the area to select
the central control address to assign and register for that timer group. Press the
button to register the selected cen-
tral control address.
1
2
17
18
33
34
49
50
8
24
40
56
9
25
41
57
10
26
42
58
16
32
48
64
[Setting fixed timer groups]
Schedule timer
1 fixed timer group (64 units together)
4 fixed timer group (16 units together)
8 fixed timer group (8 units together)
Central control address 1 – 64
Central control address 1 – 16
Central control address 1 – 8
Central control address 17 – 24
Central control address 17 – 32
Central control address 33 – 40
Central control address 33 – 48
Central control address 49 – 64
Central control address 49 – 56
Central control address 57 – 64
Central control address 41 – 48
Central control address 25 – 32
Central control address 9 – 16
5. Schedule Timer
Summary of Contents for ECO G SPW-GU055XH
Page 2: ...i ...
Page 3: ...ii ...
Page 146: ......
Page 198: ......
Page 200: ...6 2 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit 1 Electric Wiring Diagram SPW C0705DXHN8 ...
Page 201: ...6 3 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C0705DXHN8 ...
Page 203: ...6 5 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C0905 C1155DXHN8 ...
Page 205: ...6 7 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C1305 C1405DXHN8 ...
Page 207: ...6 9 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 2 Schematic Diagram SPW GU055 075 105XH ...
Page 208: ......
Page 242: ......