background image

11

Instruction Manual for IL COIL CLEAN & ITS VARIOUS MODELS

1-888-726-8869

www.sanuvox.com

How to Clean your Product

For optimal performance, the lamp(s) should be kept free of dust and residue deposit. Clean when necessary with mild soap or 

alcohol. To clean the unit exterior, use a damp cloth with general purpose detergent. Always spot test the cleaner to make sure 

it does not damage the surface.

 CAUTION: Under no circumstance should water be sprayed or splashed onto the product.

STORAGE

The IL Coil Clean and its various models does not require specific storage. It is a permanent unit that works continuously when 

powered.

 CAUTION: Keep away from unsupervised children. This unit is not a toy.

ULTRAVIOLETS: UVC

The UVC (254 nm) wavelengths produced by Sanuvox UV units and systems are the same as the ultraviolets produced by the 

Sun. The UVC attacks the micro-organisms on a molecular level deactivating the contaminants. Unlike conventional UV lamps 

on the market, Sanuvox UV units and systems use a patented process designed to deliver the maximum UV dosage to the 

moving airstream or surface.

 CAUTION: Never expose eyes or skin to an operating UV lamp.

ELECTRICAL RATINGS, POWER CONSUMPTION & AVAILABLE VOLTAGE

The IL Coil Clean and its various models has a power consumption that varies according to its lamp length: 1.0 amps for 40" 

lamps, 1.25 amps for 50" lamps and 1.5 amps for 60" lamps.

See product label to confirm power consumption of your specific unit or system.

NOTE: IF YOU EXPERIENCE A PROBLEM, PLEASE CONTACT CUSTOMER SERVICE FIRST OR SEE YOUR WARRANTY. 

DO NOT RETURN THE PRODUCT TO THE ORIGINAL PLACE OF PURCHASE. DO NOT ATTEMPT TO OPEN THE 

PRODUCT OR TAMPER WITH ITS COMPONENTS WITHOUT CONTACTING CUSTOMER SERVICE FIRST. DOING SO 

MAY VOID YOUR WARRANTY AND CAUSE PERSONAL INJURY OR DAMAGE TO THE PRODUCT.

Problem

Possible Cause

Solution

LED on ballast box is YELLOW.

- The UV lamp needs replacement.

- Replace UV lamp.

LED on ballast box is FLASHING RED.

- The UV lamp has failed or the unit 

is powered ON without any UV lamp 

installed.

- Make sure there is a UV lamp installed 

in the unit.

- Replace UV lamp.

LED on ballast box is OFF.

- There is no power delivered to the unit 

or power supply is defective.

- Make sure there is power to the unit.

- Replace power supply.

Contact your contractor for all your needs in terms of replacement parts: 

UV lamps, Anodized Aluminum Parabolic Reflector, Clamp Assembly, Lamp Boots, etc.

TROUBLESHOOTING

If your product is not working properly, refer to the following.

What you will need

A Phillips No. 2 screwdriver, a non-magnetic 5/16" nutdriver and spare parts.

Summary of Contents for IL COIL CLEAN

Page 1: ...d to the UV unit or system and all other safety precautions considered as best practices in the HVAC industry if applicable 9 When applicable local regulation may comprise more restrictive installation and or certification requirements The aforementioned requirements prevail on those of this document and the installer agree to conform to these at his own expense 10 Follow all the safety instructio...

Page 2: ...ion 5 Using the Coupler to Join Multiple 3 4 Support Rods 8 Step by Step Coupler Installation 8 OPERATION 9 How to Operate your Product 9 How to Read the LED Status Display 9 Dry Contacts for Building Automation Integration 9 MAINTENANCE 10 How to Replace Lamp s 10 Step by Step Lamp Replacement 10 How to Clean your Product 11 STORAGE 11 ULTRAVIOLETS UVC 11 ELECTRICAL RATINGS POWER CONSUMPTION AVAI...

Page 3: ...models are specialized products a sizing calculation must be prepared with your Sanuvox representative for your specific installation For information or recommendations on how to size your specific application please call SANUVOX at 1 888 726 8869 COMPONENTS How it Works The IL Coil Clean is an industrial evaporator coil cleaner that is installed in front of the coil of the air treatment systems I...

Page 4: ...ean orMULTI ILCoilClean aluminum extrusion a packaged UV lamp a support rod a ballast box and a basic installation kit The installation kit includes a UV caution decal a maintenance decal cotton gloves hex bolts 2 Phillips head screws 2 self tapping screws 2 nuts 2 lock washers 2 electrical connectors 2 clamp assemblies 2 mounting flanges 2 and a coupler Setup While selecting the appropriate locat...

Page 5: ...stalled vertically more rods and flanges are needed 3 Measure and cut the rod to desired length or assemble several rods using couplers if necessary NOTE For lengths over 66 or when using multiples IL Coil Clean units multiple support rods may be joined together by using a coupler included Refer to Using the Coupler to Join Multiple 3 4 Support Rods on page 8 4 Place the mounting flanges on both e...

Page 6: ... the mounting flanges Recommendations To ensure you protect users from direct UV exposure use a interlok switch on the access door The switch will stop the operation of the IL Coil Clean when the door is opened 10 Installation of the ballast box Remove the Phillips screws 4 from the ballast box cover Set aside the bag containing the Gaynor plug and lamp boot Mount the ballast box outside the air h...

Page 7: ...to the connection The lamp boot does not cover the entire end cap of the UV lamp but only approximately 3 4 15 There remains only the connection of the power supply which must be carried out by a certified electrician With the ballast box cover removed install a connector on the round knockout on the bottom of the ballast box Next pull an appropriate power cable into the box Insert the white neutr...

Page 8: ...embly is completed with the coupler tube inside thus joining two support rods You can now install IL units with longer support rods STEP 1 STEP 2 STEP 3 STEP 4 Using the Coupler to Join Multiple 3 4 Support Rods In the event that the AHU side panels that supports the IL Coil Clean assembly are wider than the included 3 4 support rod or that the installation required multiple IL Coil Clean units th...

Page 9: ...ast you will notice only one wire set in the ballast box as well as a black cap covering the second LED emplacement If there is two 2 ballasts there will be two wire set and two LED GREEN UV UNIT ON The unit is functioning normally YELLOW UV LAMP NEEDS REPLACEMENT Notifies the user that the UV lamp has reached the end of its lifespan and must be replaced FLASHING RED UV LAMP FAILURE Lamp has faile...

Page 10: ...ut gloves Step by Step Lamp Replacement 1 Disconnect all power before performing any maintenance or service With the power off remove the lamp from the reflector and unplug it 2 Release the old lamp from the reflector brackets and remove it CAUTION Use caution when removing and inserting UV lamps from the metal spring clamps 3 Use a new UV lamp Plug in the new lamp and place the rubber tip over th...

Page 11: ...N AVAILABLE VOLTAGE The IL Coil Clean and its various models has a power consumption that varies according to its lamp length 1 0 amps for 40 lamps 1 25 amps for 50 lamps and 1 5 amps for 60 lamps See product label to confirm power consumption of your specific unit or system NOTE IF YOU EXPERIENCE A PROBLEM PLEASE CONTACT CUSTOMER SERVICE FIRST OR SEE YOUR WARRANTY DO NOT RETURN THE PRODUCT TO THE...

Page 12: ...anty does not cover damage resulting from any unauthorized attempts to repair or from any use not in accordance with the instruction manual D This warranty does not cover the filters pre filters or other accessories if included except for material or workmanship defects Call us toll free at 1 888 726 8869 or email info sanuvox com Please be sure to specify product name NOTE IF YOU EXPERIENCE A PRO...