23
4
Inverter
Fan Fault
Protection
Line/
Inv. mode
Fan Locked
Fan Defected
2beep/2s,
and
continue for
1min
Beep
continuously
Manual
--
5
Inverter
Over
Temp
Protection
Line/
Inv. mode
HEAT SINK
over temp
--
Beep
continuously
Auto
HEAT SINK
Temp≤ 55
℃
6
Output
Abnormal
Inv. mode
(Output
Voltage
<170Vrms and
output current
under 32Arms)
or Output
Voltage >280V
rms
--
Beep
continuously
Manual
--
7
Bus Over
Protection
Standby/
Line/
Inv. mode
Bus voltage
over/ AC
Input and
output
reconnect
--
Beep
continuously
Manual
--
11
SCC
charger
over
current
SCC
SCC charger
current over
120A
--
Beep
1time/2Seco
nd
Manual
--
12
SCC over
temp.
SCC
SCC NTC
Temperature
over 110
℃
--
Beep
1time/2Seco
nd
Manual
--
13
SCC
Output
over
voltage
SCC
SCC Output
voltage over
30V(3K)/60V(
5K)
--
Beep
1time/2Seco
nd
Manual
/
Auto
SCC Output
voltage lower
than 24V(3K)/
48V(5K)
14
SCC PV
input over
voltage
SCC
PV Input
voltage over
80V(3K)/150
V(5K)
--
Beep
1time/2Seco
nd
Manual
/
Auto
PV Input
voltage lower
than 70V(3K)/
140V(5K)
15
SCC Fan
Fault(Only
for 5K
SCC)
SCC
SCC Fan lock
--
Beep
1time/2Seco
nd
Manual
--
Note: when SCC Fault, press ENTER Key will clear this fault message.
1) Unit will shut down after alarm for 1min, when unit on both fault mode and
Switch-off mode.
2) Unit will shut down immediately without any alarm, when unit on Switch-on
mode with low DC input.
Input voltage setting:
(1)
Normal
“170V~280V”for is for valuable electronic devices. If the utility is
higher or lower than this range, the unit will transfer to inverter mode
automatically.