![Santak SMAX 3000 User Manual Download Page 18](http://html1.mh-extra.com/html/santak/smax-3000/smax-3000_user-manual_810028018.webp)
14
06
Max charging
current:
To configure
total charging
current for
solar and
utility
chargers:
(Max.
charging
current=utility
charging
csolar
charging
current)
Options in SMAX 3000 model:
20A/30A/40/50A/60A(default)/70A/
80A/90A/100A
Options in SMAX 5000 model:
20A/30A/40/50A/60A(default)/70A/
80A/90A/105A
07
Max utility
charging
current
Options in SMAX 3000 model:
0A/2A/10A/20A(default)
Options in SMAX 5000 model:
0A/2A/10A/25A (default)
08
Auto restart
when
overload
occurs
Restart disable(default):
When unit is overload, unit will release
overload alarm, then turn off output &
release fault alarm, unit won’t restart
again until end-user reduce load & press
unit’s on/off power switch.
Restart enable:
When unit is overload, overload alarm 5
seconds and turn off output for 15
seconds, then restart unit again. The
restart cycle is 5 times.
09
Low DC cut
off voltage
Auto(default):
If setting auto, low DC cut off voltage will
be relate to load percent.
20.0V for 24V model @ >=60%load
21.0V for 24V model @ <60%load
40.0V for 48V model @ >=60%load
42.0V for 48V model @ <60%load
24V model:
20.0V to 24.0V, 0.2V per step;
48V model:
40.0V to 48.0V, 0.4V per step.
10
LCD backlight
control
Backlight auto(default):
LCD backlight will be off when no LCD
button is pressed after 1min.
Backlight all on