background image

s30nmdl2sm-rev0614 

                                                 Model S30 Non-Metallic Page 16

SPILL CONTAINMENT FOR PTFE 

EQUIPPED PUMPS CONCEPT

The Spill Containment option 

prevents the air end components from 

being contaminated or damaged when 

a pumping diaphragm ruptures while 

pumping caustic or toxic materials. It 

also helps to protect the environment. 

With the installation of optional leak 

detectors (either mechanical or 

electronic) the diaphragm rupture can 

be detected. The pump can then be 

shut down and repaired before any 

caustic or toxic materials can enter 

the air end and be exhausted into the 

surrounding environment.

SPILL CONTAINMENT OPTION 

DIAPHRAGM SERVICING

 

To service the diaphragms first 

shut off the suction, then shut off the 

discharge lines to the pump. Next shut 

off the compressed air supply, bleed 

the pressure from the pump, and 

disconnect the air supply line from the 

pump. Drain any remaining pumped 

liquid from the pump. Remove the pump 

before servicing.

Next, drain the fluid from the Spill 

Containment chambers. This can be 

done by removing the bottom plug 

(item 50) from each Spill Containment 

chamber.

After the fluid from the Spill 

Containment chambers has been 

drained, the wet end components 

can now be removed. See diaphragm 

servicing section for detailed 

instructions. The Spill Containment 

option has two additional virgin PTFE 

pumping diaphragms (item 46). 

FILLING  SPILL CONTAINMENT 

CHAMBERS WITH LIQUID

THE CHAMBERS ARE FILLED 

WITH WATER AT THE FACTORY.

If you prefer to substitute another 

liquid, to prevent system contamination 

consult  the  factory  first  to  determine 

compatibility of the substitute with 

pump construction.

Follow the steps listed here to 

replace the liquid in the pump after 

disassembly or liquid loss:

1. Drain the fluid in the Spill 

Containment chambers by removing 

the bottom two boss plugs (items 50). 

Replace the bottom two boss plugs 

after the fluid is drained.

2. Remove the eight capscrews 

(item 11) fastening the discharge 

manifold and elbows to the outer 

chambers (items 15). The discharge 

manifolds and elbows can now be 

removed.

3. Remove the top two boss plugs 

(items 50). The Spill Containment 

chambers are filled through the 

exposed ports.

4. Apply air pressure to the air 

distribution valve. Install safety clip 

(item 1-F) into the smaller unthreaded 

hole in one end cap. This locks the 

valve spool to one side, keeping the 

pump from shifting.

5.  Face the side of the pump with 

the installed safety clip. If the safety 

clip is installed in the top end cap, fill 

the left spill containment chamber. If 

the safety clip is installed on the bottom 

end cap, fill the right Spill Containment 

chamber. The volume of fluid is 3770 

ml  (127.5  fl.  oz.).  It  is  important  that 

the exact amount

 of fluid is used. Too 

little or too much fluid causes premature 

diaphragm failure and erratic pumping.

6. Loosely reinstall one boss plug  

to the filled Spill Containment chamber.

7. Shut off air supply. Remove safety 

clip. Adjust the air line regulator so that 

air pressure slowly fills the pump. The 

diaphragm  expands,  forcing  the  fluid 

in the chamber to be slowly displaced. 

When the pump shifts to the opposite 

side, quickly install the safety clip.

8. Loosen the top boss plug on the 

filled chambers. This allows fluid in the 

chamber to purge trapped air from the 

chamber. This can be seen by watching 

the  column  of  fluid  in  the  sight  tube. 

When  fluid  appears  at  the  top  of  the 

port, quickly tighten the boss plug. Fluid 

loss of 1 to 2ml is acceptable.

9. Tilt the pump so the uppermost 

pipe tee (item 53) is in the vertical 

position. Loosen the pipe plug (item 

49). This will allow trapped air to 

purge through the pipe tee. When fluid 

appears at the tee opening, reinstall 

the pipe plug.

NOTE:

 If all air is not purged using 

this procedure, remove the check valve 

components from the top port of the 

outer chamber (item 15). Apply manual 

pressure to the pumping diaphragm by 

inserting a blunt instrument into the top 

port of the outer chamber and applying 

pressure to the diaphragm. Loosen the 

pipe  plug  (item  49)  allowing  the  fluid 

to purge any remaining trapped air. 

Reinstall the plug.

10. Repeat steps 5 through 9 to fill 

opposite Spill Containment chamber.

11. Reinstall the check valve 

components, discharge manifold and 

elbows to the pump. The pump is now 

ready for operation.

Read these instructions 

c om ple t e ly,  be for e 

installation and start-up. 

It is the responsibility of 

the purchaser to retain 

this manual for reference. Failure to 

comply with the recommendations stated 

in this manual will damage the pump, and 

void factory warranty.

IMPORTANT

Summary of Contents for S30

Page 1: ...st 21 Air Distribution Valve with Stroke Indicator Servicing 22 Solenoid Shifted Air Valve Drawing 23 Solenoid Shifted Air Valve Parts List 23 Solenoid Shifted Air Distribution Valve Option 24 Pilot Valve Assembly Drawing 25 Pilot Valve Assembly Parts List 25 Pilot Valve Servicing 26 Diaphragm Service Drawing Non Overlay 27 Diaphragm Service Drawing with Overlay 27 Diaphragm Servicing 28 Overlay D...

Page 2: ......

Page 3: ...ACITY 0 to 238 US gallons per minute 0 to 901 liters per minute AIR VALVE No lube no stall design SOLIDS HANDLING Up to 71 in 18mm HEADS UP TO 100 psi or 231 ft of water 7 bar or 70 meters DISPLACEMENT STROKE 9 US gallon 3 41 liter CAUTION Maximum Operating Temperature Limit is 180 F for Polypropylene and 250 F for PVDF Models Air Inlet Side View Air Exhaust Side View Quality System ISO 9001 Certi...

Page 4: ...earance Air Valve with Sound Dampening Muffler 5 Expanded Clearance Air Valve w Mesh Muffler S30 Non Metallic Design Level 2 Ball Valve Explanation of Pump Nomenclature Kit Options 00 None P0 10 30VDC Pulse Output Kit P1 Intrinsically Safe 5 30VDC 110 120VAC 220 240VAC Pulse Output Kit P2 110 120 or 220 240VAC Pulse Output Kit E0 Solenoid Kit with 24VDC Coil E1 Solenoid Kit with 24VDC Explosion Pr...

Page 5: ...Y U S Gallons per minute Liters per minute BAR PSI HEAD NPSHR METERS FEET MODEL S30 Non Metallic Performance Curve Performance based on the following elastomer fitted pump flooded suction water at ambient conditions The use of other materials and varying hydraulic conditions may result in deviations in excess of 5 40 PSI 2 72 Bar 20 PSI 1 36 Bar 80 PSI 5 44 Bar Air Inlet Pressure 100 PSI 6 8 Bar 6...

Page 6: ...NGE CONFIGURATION 3 4 DIA 4 HOLES EQUALLY SPACED ON A 6 DIA BOLT CHANGE STANDARD INTEGRAL MUFFLER 1 NPT EXHAUST PORT FOR OPTIONAL MUFFLER STYLES OR PIPING EXHAUST AIR IN SUBMERGED APPLICATIONS Dimensions S30 Non Metallic Dimensions in Inches Dimensional tolerance 1 8 Note Porting Flanges are also available with PN10 80mm DIN bolting configuration Note Dimensions A is from the vertical center line ...

Page 7: ...PLACES BOTTOM VIEW SIDE VIEW FRONT VIEW SUCTION PORT 3 STANDARAD 125 FLANGE CONFIGURATION 3 4 DIA 4 HOLES EQUALLY SPACED ON A 6 DIA BOLT CHANGE STANDARD INTEGRAL MUFFLER 1 NPT EXHAUST PORT FOR OPTIONAL MUFFLER STYLES OR PIPING EXHAUST AIR IN SUBMERGED APPLICATIONS AIR INLET 3 4 NPT Note Porting Flanges are also available with PN10 80mm DIN bolting configuration Note Dimensions A is from the vertic...

Page 8: ...IEW SUCTION PORT 3 STANDARAD 125 FLANGE CONFIGURATION 3 4 DIA 4 HOLES EQUALLY SPACED ON A 6 DIA BOLT CHANGE STANDARD INTEGRAL MUFFLER 1 NPT EXHAUST PORT FOR OPTIONAL MUFFLER STYLES OR PIPING EXHAUST AIR IN SUBMERGED APPLICATIONS Dimension Standard Pump A B 6 9 16 6 9 16 Pulse Output Kit Sound Dampening Muffler Mesh Muffler 12 11 16 12 11 16 13 3 4 22 9 32 8 13 16 14 15 16 Note Porting Flanges are ...

Page 9: ...3 STANDARAD 125 FLANGE CONFIGURATION 3 4 DIA 4 HOLES EQUALLY SPACED ON A 6 DIA BOLT CHANGE STANDARD INTEGRAL MUFFLER 1 NPT EXHAUST PORT FOR OPTIONAL MUFFLER STYLES OR PIPING EXHAUST AIR IN SUBMERGED APPLICATIONS Metric Dimensions S30 Non Metallic with Spill Containment Dimensions in Millimeters Dimensional tolerance 3mm Dimension Standard Pump A B 167mm 167mm Pulse Output Kit 322mm 322mm Sound Dam...

Page 10: ...ible hose reduces vibration and strain to the pumping system A surge suppressor is recommended to further reduce pulsation in flow AIR SUPPLY Air supply pressure cannot exceed 100 psi 7 bar Connect the pump air inlet to an air supply of sufficient capacity and pressure required for desired performance When the air supply line is solid piping use a short length of flexible hose not less than 13mm i...

Page 11: ...51 000 Filter Regulator Air Dryer Available from Warren Rupp CAUTION The air exhaust should be piped to an area for safe disposition of the product being pumped in the event of a diaphragm failure INSTALLATION GUIDE Top Discharge Ball Valve Unit 2 Surge Suppressor Limited to 100 psi ...

Page 12: ...g and all other openings and connections Be certain the air supply is locked out or made non operational so that it cannot be started while work is being done on the pump Be certain that approved eye protection and protective clothing are worn all times in the vicinity of the pump Failure to follow these recommendations may result in serious injury or death WARNING WARNING In the event of diaphrag...

Page 13: ...ED 361 Nitrile 363 FKM Fluorocarbon Color coded YELLOW 364 E P D M Rubber Color coded BLUE 365 Neoprene Rubber Color coded GREEN 366 Food Grade Nitrile 368 Food Grade EPDM 370 Butyl Rubber Color coded BROWN 371 Philthane Tuftane 374 Carboxylated Nitrile 375 Fluorinated Nitrile 378 High Density Polypropylene 379 Conductive Nitrile 405 Cellulose Fibre 408 Cork and Neoprene 425 Compressed Fibre 426 B...

Page 14: ...orrective Action Remove muffler screen clean or de ice and reinstall Refer to the Air Exhaust section of your pump SERVICE MANUAL What to Check Pumped fluid in air exhaust muffler Corrective Action Disassemble pump chambers Inspect for diaphragm rupture or loose diaphragm plate assembly Refer to the Diaphragm Replacement section of your pump SERVICE MANUAL What to Check Suction side air leakage or...

Page 15: ... Seals 476 140 654 WETTED END KIT Santoprene Diaphragms PTFE Overlay Diaphragms TFE Balls and TFE Seals 476 143 354 WETTED END KIT for Polypropylene Spill Containment Santoprene Diaphragms PTFE Overlay Diaphragms PTFE Pumping Diaphragms PTFE Balls and PTFE Seals 476 143 655 WETTED END KIT for PVDF Spill Containment Santoprene Diaphragms PTFE Overlay Diaphragms PTFE Pumping Diaphragms PTFE Balls an...

Page 16: ...mber Outer 2 16 196 152 307 Chamber Inner 2 196 152 309 Chamber Inner 2 196 152 332 Chamber Inner 2 17 286 077 354 Diaphragm 2 286 077 357 Diaphragm 2 18 286 078 600 Diaphragm Overlay 2 19 312 103 520 Elbow 4 312 103 552 Elbow 4 20 360 090 360 Gasket Air Inlet 1 21 360 091 360 Gasket Inner Chamber 2 22 360 092 360 Gasket Pilot Valve 1 23 360 093 360 Gasket Main Air Valve 1 24 518 133 520 Manifold ...

Page 17: ...x HD 5 8 11 x 4 00 4 45 196 156 552 Chamber Spill Containment 2 196 156 600 Chamber Spill Containment 2 46 286 079 600 Diaphragm Pumping 2 47 518 135 520 Manifold 2 518 135 520E Manifold 80mm DIN 2 518 135 552 Manifold 2 518 135 552E Manifold 80mm DIN 2 48 538 022 110 Nipple Pipe 4 538 022 308 Nipple Pipe 4 49 560 078 611 O Ring 8 50 618 003 110 Plug Pipe 4 618 003 308 Plug Pipe 4 51 618 025 110 P...

Page 18: ...Apply air pressure to the air distribution valve Install safety clip item 1 F into the smaller unthreaded hole in one end cap This locks the valve spool to one side keeping the pump from shifting 5 Face the side of the pump with the installed safety clip If the safety clip is installed in the top end cap fill the left spill containment chamber If the safety clip is installed on the bottom end cap ...

Page 19: ...6 156 552 Chamber Spill Containment 2 196 156 600 Chamber Spill Containment 2 46 286 080 354 Diaphragm Pumping 2 47 518 135 520 Manifold Spill Containment 2 518 135 520E Manifold 80mm DIN 2 518 135 552 Manifold Spill Containment 2 518 135 552E Manifold 80mm DIN 2 48 538 022 110 Pipe Nipple 4 538 022 308 Pipe Nipple 4 49 560 078 611 O ring 8 50 618 003 110 Plug Pipe 4 618 003 308 Plug Pipe 4 51 618...

Page 20: ...y air pressure to the air distribution valve Install safety clip item 1 F into the smaller unthreaded hole in one end cap This locks the valve spool to one side keeping the pump from shifting 5 Face the side of the pump with the installed safety clip If the safety clip is installed in the top end cap fill the left Spill Containment chamber If the safety clip is installed on the bottom end cap fill...

Page 21: ...675 044 115 Ring Retaining 2 1 J 710 015 115 Screw Self tapping 4 For pumps equipped with PTFE Coated Hardware 1 031 140 002 Air Valve Assembly 1 Includes all items used on 031 140 000 except 1 J 710 015 308 Screw Self tapping 4 1 H 675 044 308 Ring Retaining 2 For pumps equipped with PTFE coated hardware option 1 031 141 000 Air Valve Assembly 1 Includes all items used on 031 140 000 minus items ...

Page 22: ...hes or other contaminates Remove the sleeve if needed and replace both the sleeve and spool with a new sleeve and spool set item 1 A STEP 3 Reassembly of the air valve Install one end cap item 1 E with an o ring item 1 G and one bumper item 1 C into one end of the air valve body item 1 B Install one retaining ring item 1 H into the groove on the same end Remove the new sleeve an spool set item 1 A...

Page 23: ...360 O Ring 8 1 H 675 044 115 Ring Retaining 2 1 J 710 015 115 Screw Self Tapping 4 1 K 210 008 330 Clip Safety 1 1 M 560 029 360 O Ring 2 For Pumps with PTFE Coated Hardware 1 031 146 002 Air Valve Assembly 1 1 J 710 015 308 Screw Self Tapping 4 1 H 675 044 308 Ring Retaining 2 includes all other items on 031 146 000 above For Pumps with Alternate Mesh Sound Dampening Mufflers or Piped Exhaust 1 0...

Page 24: ...ve the sleeve if needed and replace both the sleeve and spool with a new sleeve and spool set item 1 A STEP 3 Reassembly of the air valve Install one bumper item 1 C and one end cap item 1 E with an o ring item 1 G into one end of the air valve body item 1 B Install one retaining ring item 1 H into the groove on the same end Insert the safety clip item 1 K through the small unthreaded hole in the ...

Page 25: ...DC 1 219 002 000 Solenoid Coil 120VAC 1 219 003 000 Solenoid Coil 240VAC 1 59 241 001 000 Connector conduit 1 60 170 061 115 Capscrew Hex HD 3 8 16 x 1 75 4 61 618 052 506 Plug 2 For Explosion Proof Solenoid Valve 58 219 009 001 Solenoid Coil 120VAC 60 Hz 1 219 009 002 Solenoid Coil 240VAC 60 HZ 1 219 009 003 Solenoid Coil 12VDC 1 219 009 004 Solenoid Coil 24VDC 1 219 009 005 Solenoid Coil 110VAC ...

Page 26: ...o cycle the pump s air distribution valve an electric solenoid is utilized As the solenoid is powered one of the pump s air chambers is pressurized while the other chamber is exhausted When electric power is turned off the solenoid shifts and the pressurized chamber is exhausted while the other chamber is pressurized By alternately applying and removing power to the solenoid the pump cycles much l...

Page 27: ... LIST ITEM PART NUMBER DESCRIPTION QTY 2 095 089 000 Pilot Valve Assembly 1 2 A 095 081 551 Body Pilot Valve 1 2 B 135 033 506 Bushing 2 2 C 675 055 115 Ring Retaining 2 2 D 770 049 175 Spacer 5 2 E 917 001 374 Wiper 6 2 F 775 033 506 Spool Pilot 1 Pilot Valve Assembly Drawing ...

Page 28: ...rs and spacers until they are against the installed retaining ring in the opposite end of the pilot valve body Install the remaining bushing making sure the step side faces the wiper Install the remaining retaining ring using clip ring pliers Apply a light coating of grease to the inner diameter of each wiper Also apply a light coating of grease to the outer diameter of the pilot valve spool and g...

Page 29: ...s30nmdl2sm rev0614 Model S30 Non Metallic Page 27 Diaphragm Service Drawing Non Overlay Diaphragm Service Drawing with Overlay 32 25 15 13 6 28 17 16 29 9 14 24 24 32 25 15 13 6 28 17 29 9 14 24 24 ...

Page 30: ... compensate for stress relaxation in the clamped assembly Step 5 Installing the diaphragm assemblies to the pump Make sure the bumper item 6 is installed over the diaphragm rod Threadthestudoftheonediaphragm assembly clockwise into the tapped hole at the end of the diaphragm rod item 33 until the inner diaphragm plate is flush to the end of the rod Insert rod into pump Align the bolt holes in the ...

Page 31: ...t source is at a higher level than the pump flooded suction condition pipe the exhaust higher than the product source to prevent siphoning spills See illustration 3 at right CONVERTING THE PUMP FOR PIPING THE EXHAUST AIR The following steps are necessary to convert the pump to pipe the exhaust air away from the pump Use a 8 Torx or flat screwdriver to remove the six self tapping screws item 1 J Re...

Page 32: ... abrasive wear or embedded materials Replace as needed Inspect the check balls items 3 for wear abrasion or cuts on the spherical surface The check valve seats items 38 should be inspected for cuts abrasive wear or embedded material on the surfaces of both the external and internal chamfers The spherical surface of the check balls must seat flush to the surface of the inner chamfer on the check va...

Page 33: ...l2sm rev0614 Model S30 Non Metallic Page 31 Dual Port Option Drawing 3 ANSI STYLE FLANGE CONNECTION FOUR ø 75 HOLES ON A ø6 00 BOLT CIRCLE 3 ANSI STYLE FLANGE CONNECTION FOUR ø 75 HOLES ON A ø6 00 BOLT CIRCLE ...

Page 34: ...he Dual Porting Drawing Single porting of the suction and dual porting of the pump discharge To convert the pump from the standard single suction and single discharge porting configuration to a dual discharge porting arrangement remove the only the discharge manifolds spacers and manifold seals Position the discharge elbows in the desired direction at 90 increments See arrows and optional position...

Page 35: ...0 12 32VDC To install electronic leak detectors remove the bottom NPT pipe plug on the visual sight tube item 52 Insert leak detector into the pipe tee item 56 LEAK DETECTION OPTION MECHANICAL Follow instructions found elsewhere in this manual Filling the Spill Containment Chambers when installing leak detectors Mechanical Leak Detector Installation Kit 031 023 110 To install mechanical leak detec...

Page 36: ...e Stroke Counter Batch Controller or user control devices such as a PLC The Pulse Output Kits mount directly onto the Muffler Cap on theAir Distribution Valve Assembly or onto the air valve and senses each stroke of the main spool Consult the factory for further information and availability Pulse Output Kit Drawing Pulse Output Kits 475 244 001 10 30 VDC 475 244 002 110 220 VAC 475 244 003 10 30VD...

Page 37: ...0 12 32VDC To install electronic leak detectors remove the bottom NPT pipe plug on the visual sight tube item 52 Insert leak detector into the pipe tee item 56 LEAK DETECTION OPTION MECHANICAL Follow instructions found elsewhere in this manual Filling the Spill Containment Chambers when installing leak detectors Mechanical Leak Detector Installation Kit 031 023 110 To install mechanical leak detec...

Page 38: ... hold it in place OPTION 1 530 027 000 Sound Dampening Muffler screws directly into the Air Valve body This muffler is equipped with a porous plastic element OPTION 2 530 010 000 Mesh Muffler screws directly into the Air Valve Body This muffler is equipped with a metal element OPTION 6 530 033 000 Metal Muffler screws directly into the Air Body Option 1 and 2 Option 6 Option 0 ...

Page 39: ...A Certifies that Air Operated Double Diaphragm Pump Series HDB HDF M Non Metallic S Non Metallic M Metallic S Metallic T Series G Series U Series EH and SH High Pressure RS Series W Series SMA and SPA Submersibles and Tranquilizer Surge Suppressors comply with the European Community Directive 2006 42 EC on Machinery according to Annex VIII This product has used Harmonized Standard EN809 1998 A1 20...

Reviews: