![S&P CADB-HE BASIC Series Manual Download Page 6](http://html1.mh-extra.com/html/sandp/cadb-he-basic-series/cadb-he-basic-series_manual_3121339006.webp)
6
Vertical models
The models size 4 to 27 are supplied with support feets, while the models size 45 and 60 are supplied
with a perimetral bed. This bed must be in contact with the ground or with a fl at surface. It is essential
that the weight of the equipment was distributed between all points of support to prevent unit defor-
mation.
The installer must make sure that the ceiling structure and the securing elements can bear the
weight of the unit, taking into account that it is a dynamic load.
Models 04 to 33
Model
Weight (kg)
4
149
8
185
12
192
16
237
21
335
27
372
33
422
Models 45 to 100
Model
Weight (kg)
45
597
60
730
100
862
Horizontal models of sizes 45 and 60
IMPORTANT!
Particularities in the installation of horizontal versions LH and RH
For a correct evacuation of condensation generated into the heat exchanger, it is necessary to install the
unit with a minimum slope of
3º
to the side where the extraction fan is placed: