16
7. CONTROL FUNCTIONS
MAIN ELEMENTS
Control panel includes:
General switch
Electric box including control and wiring components, with access from side panel.
FUNCTIONS
Airfl ow adjustments
Manual fans speed adjustment
Automatic fans speed adjustment in VAV mode. Fans adjust their speed from the signal measured by an external
sensor (CO
2
, Relative humidity or Temperature)
Automatic speed adjustment of the fans in COP mode (Constant Pressure). Fans adjust their speed to maintain a
constant pressure in the duct net. It is necessary to install an external TDP sensor (accessory)
BOOST function (Forced speed preset via external power free contact) (available just in models 04 to 27)
ON/OFF function (Remote ON/OFF via external power free contact)
Temperature regulation
Temperature probes integrated within the unit (supply, extract, inlet and outlet)
Bypass adjustments
Manual actuation of bypass
Automatic actuation of bypass function free-cooling/ free-heating and heat exchanger anti-freezing protection
SECURITY FUNCTIONS
Control of polluted fi lters via pressure switches (included)
Alarm display in remote control
Fault detection in temperature probes
Fault detection in fan via pressure switches (included)
Anti-frost protection of heat exchanger via bypass activation.
COMMUNICATION
Remote wiring control
ON/OFF remote digital input via external power free contact.
Alarm digital output via power free contact.
Modbus RTU (RS-485)