Selector position
Selector 1
(Low speed)
(Vdc)
Selector 2
(Medium speed)
(Vdc)
Selector 3
(High speed)
(Vdc)
Selector 4
(Balance)
0
2,1
3,5
6,5
-30 %
1
2,1
3,7
6,7
-25 %
2
2,1
3,9
6,9
-20 %
3
2,1
4,1
7,1
-15 %
4
2,1
4,3
7,3
-10 %
5
2,1
4,5
7,5
-5 %
6
2,1
4,7
7,7
0 %
7
2,1
4,9
7,9
5 %
8
2,1
5,1
8,1
10 %
9
2,3
5,3
8,3
15 %
A
2,5
5,5
8,5
20 %
B
2,7
5,7
8,7
25 %
C
2,9
5,9
8,9
30 %
D
3,1
6,1
9,1
0 %
E
3,3
6,3
9,3
0 %
F
3,5
6,5
9,5
0 %
Possible regulations depending on the position of the control selectors.
9.4.2. Modifi cation of the bypass opening setpoint (free-cooling mode)
Using the
SW4.4
selector it is possible to select between two ranges of setpoint temperatures:
6:
6:
6:
6:
21
2))
SW4.4
Predefi ned temperature range
OFF
13/18/23ºC
ON
15/20/25ºC (by default)
Once a certain range has been selected, the setpoint value is selected by pressing on the temperature
icon (See section “Remote control setting - User”.