![S&P CADB-HE BASIC Series Manual Download Page 31](http://html1.mh-extra.com/html/sandp/cadb-he-basic-series/cadb-he-basic-series_manual_3121339031.webp)
31
Nº
Reg.
Type of register
Description
Range
Data
Default
value
R/W
Comments
44
Holding Register
Not used
46
Holding Register
Tiempo de espera
post Open Bypass
1 - 40
Minutes
2
R/W
47
Holding Register
Fan speed
deceleration ramp
0,1 - 2
V/min
0,5
R/W
Clogged fi lter alarm
5
Discret input
Alarm status
0
Alarm not
active
0
R
1
Alarm active
4
Coil
Type of supervision
0
Supervision
by time
1
R/W
1
Supervision
by pressure
switch
48
Holding Register
Time to fi lter
change alarm
500 - 5000
Hours
2500
R/W
ODA sensor alarm
8
Discret input
Alarm status
0
Alarm not
active
0
R
1
Alarm active
SUP sensor alarm
9
Discret input
Alarm status
0
Alarm not
active
0
R
1
Alarm active
ETA sensor alarm
10
Discret input
Alarm status
0
Alarm not
active
0
R
1
Alarm active
EHA sensor alarm
11
Discret input
Alarm status
0
Alarm not
active
0
R
1
Alarm active