30
Nº
Reg.
Type of register
Description
Range
Data
Default
value
R/W
Comments
Fans operation mode COP
25
Holding Register
Sensor range
0 - 2500
Pascal
2500
R/W
26
Holding Register
Setpoint
0 - End of
range
Pascal
200
R/W
29
Holding Register
Kp
1 - 250
Proportional
constant
20
R/W
30
Holding Register
Ki
1 - 250
Integral
constant
20
R/W
27
Holding Register
Minimum output
0 - 5
Volts
2
R/W
28
Holding Register
Maximum output
5 - 10
Volts
10
R/W
BOOST (Only available in models 04 to 27)
8
Coil
BOOST status
0
Not active
0
R/W
1
Active
31
Holding Register
Timmer mode boost 30-600
Minutes
60
R/W
32
Holding Register
Fan speed setpoint
when boost
5 - 10
Volts
10
R/W
6
Coil
Contact CLP BOOST
/ Fans control
(Selectable through
JP6)
0
Contact NO
0 / 1
R/W
1
Contact NC
BY-PASS management
4
Discret input
By-pass status
0
Open
0
R
1
Closed
33
Holding Register
By-pass operation
mode
1
Automatic
0
R/W
2
Manual open
3
Manual
closed
3
Coil
Defi nition of
Tcontrol
0
TETA
1
R/W
Control in extract air
1
TSUP
Control in supply air
38
Holding Register
Timmer after
by-pass manual
operation
0 - 600
Minutes
480
R/W
49
Holding Register
T
ODA
5 - 20
ºC
12
R/W
Outdoor air temperature
39
Holding Register
T
SUP
minimum
5 - 20
ºC
12
R/W
Supply air minimum
temperature
40
Holding Register
T
SUP
maximum
15 - 30
ºC
30
R/W
Supply air maximum
temperature
34
Holding Register
T
SP
low
5 - 30
ºC
13 / 15
R/W
Low temperature setpoint
35
Holding Register
T
SP
medium
5 - 30
ºC
18 / 20
R/W
Medium temperature
setpoint
36
Holding Register
T
SP
high
5 - 30
ºC
23 / 25
R/W
High temperature setpoint
37
Holding Register
Active Setpoint
Temperature
1
T
SP
low
2
R/W
2
T
SP
medium
3
T
SP
high
Defrost management
6
Discret input
Defrost status
0
Not active
0
R
1
Active
41
Holding Register
T
RISK
0 - 10
ºC
5
R/W
42
Holding Register
T
SUP
min defrost
5 - 25
ºC
11
R/W