Remote Web Access
The
Remote Web Access
toggle button enables Web-user interface access via Ethernet
Port 2. This confi guration setting can only be updated by the admin user, and only after
the admin user has changed the default password. Web access via Ethernet Port 2 is
also controlled by a DNP3 binary output setpoint, which must also be enabled to allow
this traffi c. See Figure 62. Eight steps are required to enable the
Remote Web Access
function. The complete list of instructions is documented in the “Enabling the Remote
User Interface (UI)” section on pages 74 and 75.
Figure 62. The Remote Web Access toggle button.
NOTICE
If an S&C SpeedNet™ Radio is being used for the field area network radio, the
remote Web user’s computer will require an additional setting to be updated to
enable Web access . The user must reduce the MTU (maximum transmission unit)
size to a value of 500 or lower . It is recommended to use an MTU size of 500 for
optimal performance . To change the MTU size, the following command can be used
on a Windows 10 machine:
netsh interface ipv4 set subinterface “Local Area
Connection” mtu=500 store=persistent.