36 S&C Instruction Sheet 1041-540
Saving and Loading Setup Configurations
If two or more switch controls use a similar setup configuration and the same software
version, the configuration from one switch control can be saved and loaded into the
other(s). The user then only must manually adjust the setpoints that are different for
each switch control.
Complete the following steps to save a setup configuration:
STEP 1.
Determine which switch control contains the configuration to save.
STEP 2.
Connect the computer to the selected switch control and start the IntelliLink
software.
For details, see “Start IntelliLink” section in Instruction Sheet 1041-530. If the
computer is already connected to the switch control, this step can be skipped.
STEP 3.
At any IntelliLink software screen, click on the
Setup Menu
button.
STEP 4.
At the
SETUP MENU
screen, click on the
Save Data
button.
STEP 5.
In the Save Setpoints dialog box, specify a name and location for this
configuration (CFG) file, and then click on the
Save
button.
If a location is not specified, the file is saved to the same directory as the
program files for this switch control. For example, the default location for
SNCD-S0X report files is C:\ELine\SNCD-S0X\. The extension “.CFG” is added
automatically.
Note:
This process does not save the “Physical Location” on the
SETUP: Miscel-
laneous
screen, “Communications RTU Address” on the
SETUP: Communications
screen, or the sensor configuration data on the
SETUP: Sensor Configuration
screen,
if applicable.
Saving a Setup
Configuration
Complete the following steps to load a saved configuration:
STEP 1.
If necessary, connect the computer to the switch control where the configuration
will be saved, and then start the IntelliLink software.
For details, see “Start IntelliLink” section in Instruction Sheet 1041-530.
If the computer is already connected to the switch control, this step can be
skipped.
STEP 2.
From the
File
menu, choose the
Load Setpoints
option.
STEP 3.
In the dialog box, select the CFG file for the configuration to be loaded , and then
click on the
Open
button.
STEP 4.
Make any setpoint changes required for this switch control.
For details, see Instruction Sheet 1041-530.
Note:
Be sure to enter the correct
Physical Location
value on the
SETUP: Miscel-
laneous
screen, the Communications RTU Address on the
SETUP: Communications
screen, and the sensor configuration data on the
SETUP: Sensor Configuration
screen,
if applicable..
Loading a Saved
Configuration