S&C Instruction Sheet 1041-550
17
IntelliLINK
Rev. Current - Any Phase
This field displays an
Active
message when reverse current flow is detected on any single
phase.
AC Control Power Failure
This field displays an
Active
message when ac power is not present at the Power Supply/
Control I/O module. For corrective actions, see
All LEDs on the faceplate are OFF
on page 6.
Operator Failure Override
This field displays an
Active
message when the SCADA operator sends a
Failure Override
command to the switch control. This command enables the line switch to be opened and
closed by the operator even if the battery is low.
Remote Switch Set Remote
This field displays an
Active
message when the faceplate
REMOTE/LOCAL
switch is in
the
REMOTE
position.
Auto Switch Set Enabled
This field displays an
Active
message when the faceplate automatic operation
ENABLE/
DISABLE
switch is in the
ENABLE
position. A Stop Transfer condition will exist if auto-
matic operation is disabled.
Tamper Switch (Door Open)
This field displays an
Active
message when the switch control enclosure door (S&C 5801)
or low voltage cabinet door (S&C 5802/5803) is open.
Trouble Conditions
These are conditions which clearly indicate a problem, but may not prevent line switch
operation.
Battery Low
This field displays an
Active
message when the predicted battery voltage under load is below
the
Battery Low
setpoint. For more details, see the
Operations
Instruction Sheet 1041-540.
Battery Charger Bad
Call S&C. This field displays an
Active
message when the battery is being charged at an
abnormally high voltage. The PS/IO board may need to be replaced. This message also
reports when the load resistors are disconnected from the PS/IO board at J11.
Open/Close Contacts Bad [Switches 1, 2, and 3, if applicable]
This field displays an
Active
message when the
open
and
close
contacts on the line switch
are not mutually exclusive, and the switch is not in motion.