
12
S&C Instruction Sheet 1041-550
Software Troubleshooting and Error Messages
Distribution System
Line kV to 120 Vac Base Ratio
Voltage
Transformer Wiring
Delta
voltage reporting
Phase-to-Phase voltage / 120 volts*
Phase-to-Phase
Wye
voltage reporting
Phase-to-Neutral voltage / 120 volts*
Phase-to-Neutral
* For example: 12,000 volt distribution-line voltage / 120 volts = 100/1 ratio.
d. Check the Sensor Conditioning module jumper. Make sure that the correct jumper (wye
or delta) is installed for this distribution line. Make sure that the side of the jumper
with more wire loops (2 loops for wye, 3 loops for delta) is facing towards the bottom
of the enclosure.
Wires & Grounding Type
Use
Uni-grounded Wye 3-Wire System
Delta jumper(s)
Uni-grounded Wye (Primary Neutral) 4-Wire
System
Delta jumber(s)
Multi-grounded Wye 4-Wire System
Wye jumper(s)
Delta System
Phase-to-ground connected sensors
should not be used with ungrounded
delta systems.
OVERCURRENT FAULT LED failed to show a load-side fault
a. Check whether the fault was logged. Check the
OVERCURRENT FAULT: Fault Events
screen to see whether the switch control detected and took action on the fault. If it
logged the fault, go to Step B. If not, go to Step C.
b. Check when the fault cleared. Check the
OVERCURRENT FAULT: Fault Events
screen
to see whether the fault was cleared. For a normally closed switch, the faceplate
OVERCURRENT FAULT
LED turns off when all of the following are true:
•
Three-phase line voltage has been sensed
•
The switch is closed
•
Forty-five minutes have elapsed
The LED also turns off when the switch is closed and someone toggles the faceplate
REMOTE/LOCAL
switch, or clears the LED via SCADA.
For the normally open switch, the LED turns off when you do one of the following:
• Toggle
the
REMOTE/LOCAL
switch or clear the LED via SCADA. The line switch
can be open or closed.
•
Close the switch from the faceplate or via SCADA.
NOTE: You cannot clear the LED via SCADA if the
REMOTE/LOCAL
switch is in
the
LOCAL
position.
c. Check the
SETUP: Fault Detection
screen settings. If no fault was recorded, check
the values for the
Fault Detection Current Level
setpoints, and the
Fault Duration
Time Threshold
setpoints on the
SETUP: Fault Detection
screen.
Miscellaneous Problems
Summary of Contents for 5800 Series
Page 34: ...Printed in U S A...