S&C Instruction Sheet 1042-511
25
Installation
WARNING
These switches must be set to the Automatic Operation
Disable
and
Local
positions to
avoid unexpected operation of the switch(es) during installation and setup of the switch
control .
STEP 4.
Check the connection to the switch(es) by following these procedures:
(a) Check that the faceplate OPEN and CLOSED LEDs correctly indicate the actual
position of the line switch(es).
(b) Check that the faceplate ERROR DETECTED LED is not lit. This indicates, among
other things, that the switch(es) and switch control are connected and that the open/
close auxiliary contacts for each line switch are consistent (that is, one contact set
is open while the other set is closed).
If the ERROR DETECTED LED is not lit, continue with Step 6.
If the ERROR DETECTED LED is lit:
1. Connect the portable computer to the switch control and start the IntelliLink
software. See Instruction Sheet 1042-530, “S&C 5800 Series Automatic Switch
Control with IntelliTeam
®
Automatic Restoration System:
Setup
.”
2. Read the message(s) on the
Troubleshooting>Event Status
screen, and take
appropriate action to correct the problem. See Instruction Sheet 1042-550,
“S&C 5800 Series Automatic Switch Control with IntelliTeam
®
Automatic
Restoration System:
Troubleshooting
.”
3. After correcting the error condition, continue with Step 6.
STEP 5.
For S&C switches, remove the yellow Sensor Calibration sheet that came with the
switch. There will be a sheet for each set of sensors. Put a copy in the door pocket of
the control or low-voltage cabinet.
The Sensor Calibration sheet contains the serial number and magnitude/phase
correction factors for the sensors. Installers must enter this information during
switch control setup. We recommend leaving a copy of this instruction sheet in the
door pocket of the control or low-voltage cabinet.
STEP 6.
Verify line-switch operation by following this procedure:
(a) Make sure the REMOTE/LOCAL switch is in the
Local
position and the Automatic
Operation ENABLE/DISABLE switch is in the
Disable
position.
NOTICE
Be sure a normally closed line switch is bypassed, so customer outages will not occur
during switch operation testing .
Be sure momentarily closing a normally open switch is allowed, which will tie two
circuits together .
(b) Follow company operating procedures, and use the CLOSE/OPEN switch on the
switch control faceplate to manually operate the line switch. Verify visually that the
switch can be both open and closed. Check that the switch control faceplate LEDs
correctly indicate when the switch is open and closed. When testing is completed,
leave the switch in its normal position (closed or open) for team operation.
(c) If this switch control operates multiple line switches, carry out Step 6(b) for each
switch.
Summary of Contents for 5800 Series
Page 27: ...S C Instruction Sheet 1042 511 27 Installation Diagrams...
Page 28: ...28 S C Instruction Sheet 1042 511 Installation Diagrams...
Page 29: ...S C Instruction Sheet 1042 511 29 Installation Diagrams...
Page 30: ...30 S C Instruction Sheet 1042 511 Installation Diagrams...
Page 31: ...S C Instruction Sheet 1042 511 31 Installation Diagrams...
Page 32: ...32 S C Instruction Sheet 1042 511 Installation Diagrams...
Page 33: ...S C Instruction Sheet 1042 511 33 Installation Diagrams...
Page 34: ...34 S C Instruction Sheet 1042 511 Installation Diagrams...
Page 35: ...S C Instruction Sheet 1042 511 35 Installation Diagrams...
Page 36: ...36 S C Instruction Sheet 1042 511 Installation Diagrams...
Page 37: ...S C Instruction Sheet 1042 511 37 Installation Diagrams...
Page 38: ...38 S C Instruction Sheet 1042 511 Installation Diagrams...