S&C 5800 Series Installation Manual Download Page 12

12

    S&C Instruction Sheet 1042-511 

Before installing the switch control package in the field, carry out the following steps. This 
is best done in the shop before the installer leaves for the installation site.

STEP 1. 

Inspect the switch control for visible damage.

On receipt of the control, make sure there is no obvious damage to the switch 

control enclosure or any of the internal components. Also, check any switch  
interface connectors that are included with the control. If the battery will not be used 
immediately, store it in a cool, dry place, and recharge it every six months or less.

STEP 2. 

Put a copy of the source and line segment information/drawing in the door pocket of 
the control or low-voltage cabinet.

The team information sheet includes a single-line diagram of the team and the  

information you need to correctly install and configure this control.

STEP 3. 

Locate the items needed to install and set up the 5800 Series Switch Control.

The following items are required to install the software, set up the control, set up 

the communications equipment (radio, modem, etc.), and enable operation. These 
items also can be used to diagnose certain hardware problems that can occur  
during installation:

Personal Computer

— Requires Microsoft Windows

®

 7 operating system, 

Internet Explorer 5.0 or higher, 32 MB of RAM, and a USB or serial port

Serial Communication Cable

—Connects the computer to the LOCAL COMM 

port on the control (Use a straight-through cable, not a null-modem cable. The  
cable must be long enough to connect to an installed switch control.)

The serial connection is RS232 with a DB9-pin connector.
If the computer only has USB ports, use a serial to USB cable adapter.

NOTICE

S&C ships several types of software-controlled products . Make sure to use the 

 

correct software for this switch control . The latest software revisions are posted at the 
S&C website 

sandc.com/en/support/sc-customer-portal/

 .

STEP 4. 

Make sure all required communications equipment (radios, antennas, modems, 
etc.) is available.

Each team member must communicate with other team members, either by radio, 

modem, or cable. Depending on the location of the other team members, one or more 
repeater radios may be required. For more information, see the manufacturer’s 
documentation for the communication system.

STEP 5. 

Check the sensor conditioning module jumper(s) using the following procedure:

The switch control sensor conditioning module is configured with a delta/wye  

jumper. If there are three voltage sensors, the sensor conditioning mod-
ule uses one jumper. If there are six voltage sensors, such as line-side 
sensors on two switches in pad-mounted gear or Vista

®

  Underground 

Distribution Switchgear, the sensor conditioning module requires two  
jumpers.

(a)  Locate the installed sensor conditioning module jumper(s) and the alternate 

jumper(s). See Figure 4 on page 13.

Pre-Installation 

Checklist

Installation

STEP 14. 

Determine whether the number of line segments restored by a team should be 
limited.

Configure the 

Line Segment Limit

 setpoint on the 

Setup>Team

 screen to limit 

the number of line segments a team picks up. For example, “Add 1” inhibits any other 
line segments from being restored through a member after it restores its first line 
segment. Set this value to “N/A” to allow the team to pick up as many line segments 
as capacity allows.

Summary of Contents for 5800 Series

Page 1: ...2 Special Warranty Provision 2 Safety Information Understanding Safety Alert Messages 4 Following Safety Instructions 4 Replacement Instructions and Labels 4 Installation Applicable Software 5 Planni...

Page 2: ...ns of sale as set forth in Price Sheets 150 and 181 applies to the S C 6800 Series Automatic Switch Control except that the first paragraph of the said warranty is replaced by the following 1 General...

Page 3: ...s applicable instruction sheets This warranty does not apply to major components not of S C manufacture such as batteries and communication devices However S C will assign to the immediate purchaser o...

Page 4: ...if instructions including recommended precautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not f...

Page 5: ...trol or in the switch control itself during certain switchgear wiring or grounding system failures or due to a problem with the switch control itself For this reason access to switch controls should b...

Page 6: ...ion see the About Fault Detection Switch Control Setup Point 6 in Instruction Sheet 1042 531 S C 5800 Series Automatic Switch Controls With IntelliTeam II Automatic Restoration System Setup When confi...

Page 7: ...that will be part of the IntelliTeam II system Plan the communication system for peer to peer transmission and for data interchange with the SCADA master station if one is used Name the teams 16 chara...

Page 8: ...nication hardware installation instructions Start IntelliLink software and establish communication between the team member and your computer setup instructions Use IntelliLink software to enter all se...

Page 9: ...IntelliLink Remote Setup Software Is this the last team that needs to be checked Is each team where this control is a member ready for transfer Make sure all switches are in their normal configuration...

Page 10: ...STEP 6 NotethenormallyOpen Closedstateforeachteammember Enterthisinformation on the Setup Team screen STEP 7 Createalayoutofthesource s switches andlinesegmentsthatincludestheteams Every switch should...

Page 11: ...ence team members will use to restore the line segment This is an optional step used to guide the restoration process Regardless of the alternate source sequence configu ration restoration progresses...

Page 12: ...serial connection is RS232 with a DB9 pin connector If the computer only has USB ports use a serial to USB cable adapter NOTICE S C ships several types of software controlled products Make sure to use...

Page 13: ...determine which jumper is correct for the distribution system Table 2 Distribution System Jumper Selection 3 Wires Grounding Type Use Uni grounded wye system Delta jumper s 4 Wires Grounding Type Use...

Page 14: ...terior STEP 6 Check the battery using the following procedure The 5800 Series Switch Control is shipped with a Hawker Gates Monoblock 24 Vdc or 36 Vdc battery The battery is terminated with a connecto...

Page 15: ...the IntelliLink Software section in Instruction Sheet 1042 530 S C 5800 Series Automatic Switch Control with IntelliTeam Automatic Restoration System Setup STEP 2 If the switch control uses a modem fo...

Page 16: ...d in pad mounted equip ment and the switch control is only powered from the sensors skip the remainder of this instruction sheet and go directly to Instruction Sheet 1042 530 S C 5800 Series Automatic...

Page 17: ...ere elevated to primary high voltage Installers must follow the sequence of installation steps outlined in this chapter to ensure a safe and successful switch control installation STEP 3 Configure the...

Page 18: ...the low voltage compartment as follows 1 Find the four studs on the wall of the low voltage compartment 2 Position the switch control so the four studs align with the four holes in the mounting flange...

Page 19: ...nication and may optionally communicate with SCADA Installers must toggle the faceplate REMOTE LOCAL switch to the Local position to ensure the switch control does not perform remote switching command...

Page 20: ...ew battery or the battery was shipped separately install it now WARNING If the enclosure heater was recently on the battery bracket may be hot Be careful not to touch a hot bracket The battery bracket...

Page 21: ...With the ac line fuse still removed connect the red and black battery leads to the corresponding leads from the switch control This will supply dc voltage to the switch control For Scada Mate Switchin...

Page 22: ...ts at J2 and J4 See Figure 14 For installations using three voltage sensors and nine current sensors the voltage input should be connected at J3 and the current inputs at J2 J4 and J6 See Figure 14 Ch...

Page 23: ...ac line fuse is inserted the red AC ON and CHG ON LEDs should illuminate See Figure 13 on page 21 If the AC ON and CHG ON LEDs do not illuminate check the external ac voltage source if applicable The...

Page 24: ...struction Sheet 1042 550 S C 5800 Series Automatic Switch Control with IntelliTeam Automatic Restoration System Troubleshooting d Check that the LCD screen is backlit and that data are displayed Then...

Page 25: ...rrecting the error condition continue with Step 6 STEP 5 For S C switches remove the yellow Sensor Calibration sheet that came with the switch There will be a sheet for each set of sensors Put a copy...

Page 26: ...make sure the communications equipment has power For overhead switch controls the communication equipment is on the back of the faceplate For 5800 Series Switch Controls installed in pad mounted gear...

Page 27: ...S C Instruction Sheet 1042 511 27 Installation Diagrams...

Page 28: ...28 S C Instruction Sheet 1042 511 Installation Diagrams...

Page 29: ...S C Instruction Sheet 1042 511 29 Installation Diagrams...

Page 30: ...30 S C Instruction Sheet 1042 511 Installation Diagrams...

Page 31: ...S C Instruction Sheet 1042 511 31 Installation Diagrams...

Page 32: ...32 S C Instruction Sheet 1042 511 Installation Diagrams...

Page 33: ...S C Instruction Sheet 1042 511 33 Installation Diagrams...

Page 34: ...34 S C Instruction Sheet 1042 511 Installation Diagrams...

Page 35: ...S C Instruction Sheet 1042 511 35 Installation Diagrams...

Page 36: ...36 S C Instruction Sheet 1042 511 Installation Diagrams...

Page 37: ...S C Instruction Sheet 1042 511 37 Installation Diagrams...

Page 38: ...38 S C Instruction Sheet 1042 511 Installation Diagrams...

Reviews: