background image

CW-6000/6100/6200 Series

6

<4> Operation status and parameters

adjustment

The new T-506 intelligent temperature controller does not need to adjust

the controlling parameters under normal circumstance. It will self-adjust
controlling parameters according to room temperature for meeting equipment
cooling requirements.

The new T-506H intelligent temperature controller is selected constant

temperature control mode as factory setting with water temperature at 25

.

User can adjust it as needed.

T-506 and T-506H controllers are of same functions and structure except

default setting.

1. Temperature control panel introduction

(1). Indicators of temperature controller working status:

COMP

ON, compressor working

SV

ON, solenoid valve working

Heating

ON, heating rod working

INT Ctrl

ON, controller working in intelligent control mode

CT Ctrl

ON, controller working in constant temperature control mode

PARAM Set ON, controller working in parameters setting mode
ALM OUT

ON, alarm output status

Room Temp ON, displaying room temperature
ST DLA

ON, starting up delay status

(2). Press

key to show the room temperature, 6 seconds later default

display restored. (Meanwhile, Room Temp light is on, displaying room
temperature.)

(3).

keys are for modifying parameters values and

keys

are for switching parameter items.

Summary of Contents for CW-6000

Page 1: ...CW 6000 6100 6200 INDUSTRIAL CHILLER USER MANUAL...

Page 2: ...00 6200 Series 2 Contents 1 Cautions 3 2 Contour and parts introduction 4 3 Installation 5 4 Operation and parameters adjustment 6 5 Alarm and output terminal 10 6 Specifications 11 7 Simple troublesh...

Page 3: ...forbidden to run the chiller without water in the storage water tank The new machine is packed after draining whole water in the tank so please make sure the tank has water inside before machine star...

Page 4: ...Contour and parts introduction TEMPERATURE CONTROLLER WATER PRESSURE GAUGE POWER SWITCH WATER SUPPLY INLET AIR INLET FILTER GAUZE AIR OUTLET WATER INLET WATER OUTLET WATER LEVEL GAUGE DRAIN ALARM OUTP...

Page 5: ...go back to normal 2 After the first boot you must immediately check whether the water pipe leaks 3 Power switched on if the water temperature is below the set value it is normal that fans and other co...

Page 6: ...and structure except default setting 1 Temperature control panel introduction 1 Indicators of temperature controller working status COMP ON compressor working SV ON solenoid valve working Heating ON h...

Page 7: ...In alarming state the alarm sound could be suspended by pressing any button but the alarm display remains until the alarm condition is eliminated 4 Temperature controller parameters list Order Code I...

Page 8: ...8 and then press the SET key if the password is correct F0 displays entering into setup status D1 flashing to indicate that the controller is under parameters setup status If the password is incorrec...

Page 9: ...r temperature is 10 lower than normal 3 Case 3 cooling water temperature is controlled by constant mode Requiring water temperature is constant in 25 and the fluctuate does not exceed 1 The over high...

Page 10: ...less than 300V Display Condition Alarm code Buzzer OUT H1 H2 OUT H1 H3 Circulating pump works properly DISCONNECTION BREAKOVER Blocked cooling water circulation loop E6 Sounds BREAKOVER DISCONNECTION...

Page 11: ...10724Btu h 10286Btu h 9502Btu h 10724Btu h 10286Btu h 9502Btu h 10724Btu h 3 015KW 2 785KW 3 145KW 3 015KW 2 785KW 3 145KW 3 015KW 2 785KW 3 145KW 2592Kcal h 2395Kcal h 2711Kcal h 2592Kcal h 2395Kcal...

Page 12: ...14483Btu h 14092Btu h 4 24KW 4 13KW 4 24KW 4 13KW 4 24KW 4 13KW 3650Kcal h 3551Kcal h 3650Kcal h 3551Kcal h 3650Kcal h 3551Kcal h Refrigerant R 22 R 410a Refrigerant charge 950g 900g 950g 900g 950g 90...

Page 13: ...h 17510Btu h 17640Btu h 5 13KW 5 17KW 5 13KW 5 17KW 5 13KW 5 17KW 4420Kcal h 4446Kcal h 4420Kcal h 4446Kcal h 4420Kcal h 4446Kcal h Refrigerant R 22 R 410a Refrigerant charge 1100g 1200g 1100g 1200g...

Page 14: ...nlet Water circulation pipes are blocked or a pipe bending deformation Check water circulation pipe Ultrahigh water temperature alarm controller displays E2 Blocked dust gauze bad thermolysis Unpick a...

Page 15: ...CW 6000 6100 6200 Series 15...

Reviews: