CW-6000/6100/6200 Series

3

Thank

you

for

using

the

machine

from

GUANGZHOU

TEYU

ELECTROMECHANICAL CO., LTD. Please read the installation instructions

carefully before installing and operating and keep it properly.

This installation instructions is not a quality assurance. GUANGZHOU TEYU

ELECTROMECHANICAL CO., LTD reserves the right to the interpretation of

correction of typographical errors, improper mentioned information and product

improvement. The amended content will be reprinted in installation instructions

without notice in advance.

<1> Cautions

1. Please ensure that the power supply and electrical outlet are in good contact

and the earth wire must be firmly grounded!

2. Please make sure there is stable and normal voltage for the working chiller!

As the refrigeration compressor is more sensitive to the power supply and

voltage, so the operating voltage of our standard product is of 200 ~ 250V (110V

model is of 100 ~130V). If you do need a wider operating voltage range,

customization is available for us.

3. Unmatched power frequency can cause the chiller damage!

Please choose model of 50Hz or 60Hz according to actual circumstance.

4. To protect the pump, it’s strictly forbidden to run the chiller without water in the

storage water tank!

The new machine is packed after draining whole water in the tank, so please

make sure the tank has water inside before machine starting, otherwise it’s

easily to have the pump damaged. When the water level is below the green

(NORMAL) range of the water level gauge, the cooling capacity of our chiller

will go down slightly. Hence please ensure the water level is within the green

(NORMAL) range. To drain through circulating pump is strictly prohibited!

5. Please be sure that the air inlet and air outlet are in good ventilation!

There must be at least 50cm from obstructions to the air outlet which is in the

back of the cooler, and should leave at least 30cm between obstructions and

the side air inlet.

6. The filter screen must be regularly cleaned!

It’s essential to unpick and wash the dust gauze, or the serious blockage will

cause breakdown to the chiller.

7. Please pay attention to the effect of the condensate water!

With greater ambient humidity, when the water temperature is lower than the

ambient temperature, the condensate water will generate on the surface of

water circular pipes and the cooled components. If above circumstance

appears, it is recommended to set a higher water temperature or keep pipes

and cooled parts warm.

8. This product is an industrial equipment.For professional use only.

Summary of Contents for CW-6000

Page 1: ...CW 6000 6100 6200 INDUSTRIAL CHILLER USER MANUAL...

Page 2: ...00 6200 Series 2 Contents 1 Cautions 3 2 Contour and parts introduction 4 3 Installation 5 4 Operation and parameters adjustment 6 5 Alarm and output terminal 10 6 Specifications 11 7 Simple troublesh...

Page 3: ...forbidden to run the chiller without water in the storage water tank The new machine is packed after draining whole water in the tank so please make sure the tank has water inside before machine star...

Page 4: ...Contour and parts introduction TEMPERATURE CONTROLLER WATER PRESSURE GAUGE POWER SWITCH WATER SUPPLY INLET AIR INLET FILTER GAUZE AIR OUTLET WATER INLET WATER OUTLET WATER LEVEL GAUGE DRAIN ALARM OUTP...

Page 5: ...go back to normal 2 After the first boot you must immediately check whether the water pipe leaks 3 Power switched on if the water temperature is below the set value it is normal that fans and other co...

Page 6: ...and structure except default setting 1 Temperature control panel introduction 1 Indicators of temperature controller working status COMP ON compressor working SV ON solenoid valve working Heating ON h...

Page 7: ...In alarming state the alarm sound could be suspended by pressing any button but the alarm display remains until the alarm condition is eliminated 4 Temperature controller parameters list Order Code I...

Page 8: ...8 and then press the SET key if the password is correct F0 displays entering into setup status D1 flashing to indicate that the controller is under parameters setup status If the password is incorrec...

Page 9: ...r temperature is 10 lower than normal 3 Case 3 cooling water temperature is controlled by constant mode Requiring water temperature is constant in 25 and the fluctuate does not exceed 1 The over high...

Page 10: ...less than 300V Display Condition Alarm code Buzzer OUT H1 H2 OUT H1 H3 Circulating pump works properly DISCONNECTION BREAKOVER Blocked cooling water circulation loop E6 Sounds BREAKOVER DISCONNECTION...

Page 11: ...10724Btu h 10286Btu h 9502Btu h 10724Btu h 10286Btu h 9502Btu h 10724Btu h 3 015KW 2 785KW 3 145KW 3 015KW 2 785KW 3 145KW 3 015KW 2 785KW 3 145KW 2592Kcal h 2395Kcal h 2711Kcal h 2592Kcal h 2395Kcal...

Page 12: ...14483Btu h 14092Btu h 4 24KW 4 13KW 4 24KW 4 13KW 4 24KW 4 13KW 3650Kcal h 3551Kcal h 3650Kcal h 3551Kcal h 3650Kcal h 3551Kcal h Refrigerant R 22 R 410a Refrigerant charge 950g 900g 950g 900g 950g 90...

Page 13: ...h 17510Btu h 17640Btu h 5 13KW 5 17KW 5 13KW 5 17KW 5 13KW 5 17KW 4420Kcal h 4446Kcal h 4420Kcal h 4446Kcal h 4420Kcal h 4446Kcal h Refrigerant R 22 R 410a Refrigerant charge 1100g 1200g 1100g 1200g...

Page 14: ...nlet Water circulation pipes are blocked or a pipe bending deformation Check water circulation pipe Ultrahigh water temperature alarm controller displays E2 Blocked dust gauze bad thermolysis Unpick a...