1st Edition of TEMP2020_Series IM : Dec. 15. 2008 Page 45 / 71
▶
Press
(Enter) button to complete time signal setting.
▶
Press
(ESC) button to cancel input and disappear Input Keypad.
☞
Able to select and enter the required Time Signal group by pressing TS1 ~ TS8 button setting by [5.4
TIME SIGNAL SET].
Table 5-1. PATTERN SET Parameters
Parameter
Range
Unit
Default
CH1 Pattern Number
1~40
ABS
1
CH2 Pattern Number
1~40
ABS
1
Start Code
TPV, SPV, SSP
ABS
TPV
Start Condition(SSP)
#n.EU(0.0~100.0%)
#n.EU
#n.EU(0.0%)
Segment #n Target SP
#n.EU(0.0~100.0%)
#n.EU
#n.EU(0.0%)
Segment #n Time
-00.00.01(OFF) ~ 999.59.59(Hr, Min, Sec)
ABS
-00.00.01
Segment #n Time Signal 1 ~ 8
0 ~ 20
ABS
0
Segment #n Seg. Alarm 1 ~ 4
0 ~ 8
ABS
0
Segment #n Seg. PID
0 ~ 6
ABS
0
*Time Signal 8 can not be selected when use Current Output 1 or 2 Set Value as Aux. Output.
* #n : 1 ~ 99