IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 30/40
5-6-4. PID SETTING
Select PID at the
SETUP
page(Figure 5-6-1) for switching the PID page.
5-6-4-1. TEMP PID(Temp)
Figure 5-6-9 TEMP PID
①
TEMP REFERENCE(T1/T2)
: Set the boundary value about temp span of PID zone.
②
AUTO TUNING GROUP
: Go to the PID Group for PID(1~9) for change the PID value.
③
HYSTERESIS
: Set the HYSTERESIS when select PID zone.
④
DISPLAY PRESENT RUNNING PID No.
☞
Ex) Auto Tuning can be doing only on Fix running, Auto Tuning is doing with SP and
the result will be saved automatically on the zone which is for SP.
⑤
Tuning point : Refer
⑤
Tuning point on HUMI PID for detail function.
☞
HRL < HSP < H1 &
T.RL
≤
NSP < T1 than
PID GROUP 1
T1
≤
NSP < T2 than
PID GROUP 4
T2
≤
NSP < T.RH than
PID GROUP 7
☞
H1 < HSP < H2 &
T.RL
≤
NSP < T1 than
PID GROUP 2
T1
≤
NSP < T2 than
PID GROUP 5
T2
≤
NSP < T.RH than
PID GROUP 8
☞
H2 < HSP < H.RH &
T.RL
≤
NSP < T1 than
PID GROUP 3
T1
≤
NSP < T2 than
PID GROUP 6
T2
≤
NSP < T.RH than
PID GROUP 9
☞
NSP=0
℃
Æ
Saved PID GROUP1, NSP=100
℃
Æ
Saved PID GROUP 9
(Table 5-10) TEMP TUNE PARAMETER
Name
Function
Valid Range
Unit
Default Value
T1
TEMP REFERENCE 1
T.EU (0~100%)
T.EU
T.EU (0%)
T2
TEMP REFERENCE 2
T.EU (0~100%)
T.EU
T.EU (0%)
RHY
HYSTERESIS BAND
T.EU (0~10%)
T.EU
T.EU (0.5%)
TUNING POINT
AT TUNING POINT
T.EUS (0.01~1.00%)
T.EUS
T.EUS(0.1%)
Go to HUMI TUNE page (Figure 5-6-9)
②
①
③
④
⑤