II.USERS
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 24/40
■
INPUT_HUMI
Figure 5-6-3 HUMI INPUT
①
SENSOR
: Select kinds of humi. sensor.
②
HUMI RANGE
: Set the range of humi.
③
HUMI FILTER
:To remove the noise from the high-frequency of noise in the humi data.
④
BIAS
: Bias about the humidity.
⑤
SCALE
(DCV ONLY)
: As DCV sensor type, set the scale for range.
(Table 5-8) INPUT_HUMI PARAMETER
Name
Function
Valid Range
Unit
Default Value
H.SENSOR
HUMI SENSOR
PT, DCV
ABS
PT
H.RH
HUMI RANGE HIGH
H.EU(0 ~ 100%)
H.EU
H.EU(100%)
H.RL
HUMI RANGE LOW
H.EU(0 ~ 100%)
H.EU
H.EU(0%)
H.BIAS
HUMI BIAS
H.EUS(-20 ~ 20%)
H.EU
H.EUS(0%)
H.FILTER
HUMI FILTER
0 ~ 120S
ABS
0
H.SCALE
HUMI HIGH SCALE
0.1 ~ 100.0
%
100.0 (%)
L.SCALE
HUMI LOW SCALE
0.0 ~ 99.9
%
0.0(%)