![Samwontech TEMI770 Manual Download Page 46](http://html1.mh-extra.com/html/samwontech/temi770/temi770_manual_3793449046.webp)
II.USERS
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 27/40
5-6-2. OUTPUT
5-6-2-1.Output
Select
OUTPUT
at the SETUP page(Figure 5-6-1) for switching the OUTPUT page.
Figure 5-6-5 OUTPUT
①
OUTPUT
: Output type.(SSR/SCR)
②
DIRECTION
: Select of PID direction (Reverse/Forward)
③
CYCLE
: Set output cycle. It is only for SSR type.
④
ANTI RESET WIND-UP(Excess integration prevention)
: The larger setting, the sooner PID computation (integral computation) stops.
Used when the control output travels up to 100% or down to 0(zero)% and
stays at this point.
⑤
AT GAIN
: Set the gain value when setting PID parameter with
AUTO TUNING.
Decrease the gain value for quick response,
or increase the gain value for stable PID value.(See Figure 5-6-5-1)
(Table 5-9) OUTPUT PARAMETER
Name
Function
Valid Range
Unit
Default Value
T.DIRECT
TEMP DIRECT
REVERSE, FORWARD
ABS
REVERSE
H.DIRECT
HUMI DIRECT
REVERSE, FORWARD
ABS
REVERSE
T.OUTPUT
TEMP OUTPUT
SSR, SCR
ABS
SSR
H.OUTPUT
HUMI OUTPUT
SSR, SCR
ABS
SSR
T.CYCLE
TEMP CYCLE
1 ~ 1,000
ABS
1
H.CYCLE
HUMI CYCLE
1 ~ 1,000
ABS
1
ARW
ANTI RESET WINDUP
0(AUTO), 50.0 ~ 200.0
ABS
0(AUTO)
AT GAIN
AUTO TUNING GAIN
0.1 ~ 10.0
ABS
1.0
Gain < 1
Gain = 1
Gain > 1
Figure 5-6-5-1
Figure 5-6-6 RET