SAMWONTECH
1st Edition of TEMI2000_Series IM : Dec. 15. 2008 Page 37 / 58
7.11 OUTPUT Group
This INPUT group is used for setting parameter D-Register for control output and retransmission.
█
OUTPUT setting D-Register
D-Reg.
Symbol
Descriptions
D1001
TEMP.OUT
Temperature Control OUTPUT type
D1002
TEMP.DIR
PID Control DIRECTION (FWD/REV) for temperature
D1003
TEMP.CT
Pulse CYCLE TIME when‘SSR’temperature Control Output
D1004
TEMP.ARW
ARW (Anti Reset Wind-up) function for temperature
D1005
TEMP.ATG
Temperature Auto-Tuning GAIN value for Manual PID
D1008
HUMI.OUT
Humidity Control OUTPUT type
D1009
HUMI.DIR
PID Control DIRECTION (FWD/REV) for humidity
D1010
HUMI.CT
Pulse CYCLE TIME when‘SSR’ humidity Control Output
D1011
HUMI.ARW
ARW (Anti Reset Wind-up) function for humidity
D1012
HUMI.ATG
Humidity Auto-Tuning GAIN value for Manual PID
D1015
TEMP.RETT
Target TYPE of temperature retransmission
D1016
TEMP.RETH
Range HIGH of temperature retransmission
D1017
TEMP.RETL
Range LOW of temperature retransmission
D1020
HUMI.RETT
Target TYPE of humidity retransmission
D1021
HUMI.RETH
Range HIGH of humidity retransmission
D1022
HUMI.RETL
Range LOW of humidity retransmission
D1025
RET.SEL
Target object of retransmission.